5-14 Terminal 32 Digital Input
Option:
Function:
[0]
*
No operation
[1]
Reset
[8]
Start
[23]
*
Set-up select bit
0
Select Set-up select bit 0 or Select Set-
up select bit 1 to select one of the four
set-ups. Set
to Multi Set-up.
[24]
*
Set-up select bit
1
(Default Digital input 32): Same as Set-
up select bit 0 [23].
5-15 Terminal 33 Digital Input
Option:
Function:
[0]
*
No operation
[1]
Reset
[8]
Start
[23]
*
Set-up select bit
0
Select Set-up select bit 0 or Select Set-
up select bit 1 to select one of the four
set-ups. Set
to Multi Set-up.
[24]
*
Set-up select bit
1
(Default Digital input 32): Same as Set-
up select bit 0 [23].
6.4.2 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in parameter
5-01 Terminal 27 Mode
, and set
the I/O function for terminal 29 in
5-02 Terminal 29 Mode
.
These parameters cannot be adjusted while the AFE is
running.
5-30 Terminal 27 Digital Output
Option:
Function:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control board receives supply
voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal
on the control board.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[252]
Regen limit
Active when actual regenerative power
is above the value set in parameter
4-52
Warning Regen Limit
[253]
Power limit
Active when actual active power is
above the value set in parameter
4-53
Warning Power Limit
.
[254]
Soft charge
ready
DC bus charged
[255]
*
DC-link on ref.
AFE running and motor operation
allowed.
5-31 Terminal 29 Digital Output
Option:
Function:
[0]
*
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control board receives supply
voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[252] Regen limit
Active when actual regenerative power is
above the value set in parameter
4-52
Warning Regen Limit
[253] Power limit
Active when actual active power is above
the value set in parameter
4-53 Warning
Power Limit
.
[254] Soft charge
ready
DC bus charged
[255] DC-link on ref.
AFE running and motor operation
allowed.
In this parameter, the function for the terminal 29 digital
output is selected.
6.4.3 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays
(Relay 1 [0], Relay 2 [1])
5-40 Function Relay
Option:
Function:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control board receives supply
voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[252]
Regen limit
Active when actual regenerative power
is above the value set in parameter
4-52
Warning Regen Limit
[253]
Power limit
Active when actual active power is
above the value set in parameter
4-53
Warning Power Limit
.
[254]
*
Soft charge
ready
DC bus charged
[255]
DC-link on ref. AFE running and motor operation
allowed.
In this parameter, the function for the relay outputs is
selected. The selection of each mechanical relay is realised
in an array parameter.
How to Programme
Operating Instructions
50
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG33X402