6.2.4 0-4* LCP Keypad
Enable, disable and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled Key disabled avoids accidental usage of the key.
[1]
*
Enabled
[Hand On] key enabled
[2]
Password Avoid unauthorised start in Hand mode. If
parameter 0-40 [Hand on] Key on LCP
is included
in My Personal Menu, define the password in
0-65 Personal Menu Password
. Otherwise, define
the password in
.
0-41 [Off] Key on LCP
Option:
Function:
[0]
Disabled Avoids accidental stop of the AFE.
[1]
*
Enabled
[2]
Password Avoids unauthorised stop. If
0-41 [Off] Key on LCP
is included in the Quick Menu, then define the
password in
.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled avoid accidental start of the AFE in Auto mode.
[1]
*
Enabled
[2]
Password Avoids unauthorised start in Auto mode. If
0-42 [Auto on] Key on LCP
is included in the
Quick Menu, then define the password in
parameter 0-65 Quick Menu Password
.
0-43 [Reset] Key on LCP
Option:
Function:
[0] Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1] Enabled
[2] Password
Avoids unauthorised resetting. If
parameter 0-43 [Reset] Key on LCP
is included
in the Quick Menu, then define the password
in
parameter 0-65 Quick Menu Password
[7] Enabled
without OFF
Resets the AFE without setting it in
Off
mode.
[8] Password
without OFF
Resets the AFE without setting it in
Off
mode.
A password is required when pressing [Reset]
(see [2]).
6.2.5 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from one
frequency converter to another.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
[2]
All from LCP
[3]
Size indep. from LCP
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy to set-up 1
[2]
Copy to set-up 2
[3]
Copy to set-up 3
[4]
Copy to set-up 4
[9]
Copy to all
6.2.6 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
*
[-9999 -
9999 ]
Define the password for access to the Main
Menu via the [Main Menu] key. If
0-61 Access to Main Menu w/o Password
is
set to
[0] Full access
, this parameter is
ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter 0-60 Main Menu Password
[1]
LCP: Read
only
Prevent unauthorised editing of Main Menu
parameters.
[2]
LCP: No
access
Prevent unauthorised viewing and editing of
Main Menu parameters.
[3]
Bus: Read
only
Read-only functions for parameters on
Fieldbus and/or FC standard bus.
[4]
Bus: No
access
No access to parameters is allowed via
Fieldbus and/or FC standard bus.
[5]
All: Read only Read-only function for parameters on LCP,
Fieldbus or FC standard bus.
[6]
All: No access No access from LCP, Fieldbus or FC standard
bus is allowed.
If
[0] Full access
is selected,
,
0-65 Personal Menu Password
and
0-66 Access to
Personal Menu w/o Password
are ignored.
NOTICE
A more complex password protection is available for
OEMs upon request.
How to Programme
Operating Instructions
46
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG33X402