6.2 Parameters: 0-** Operation and Display
Parameters related to the basic functionality of the AFE.
Parameters related to the function of the display and
buttons.
6.2.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the display.
[0]
*
English Part of Language packages 1 - 4
6.2.2 0-1* Set-up Operations
Define and control the individual parameter setups.
0-10 Active Set-up
Option:
Function:
Select the set-up to control the frequency
converter functions.
[0]
Factory
setup
Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a known
state.
[1]
*
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four
separate parameter set-ups within which all
parameters can be programmed.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-
up
Remote selection of set-ups using digital
inputs and the serial communication port.
This set-up uses the settings from
0-12 This
Set-up Linked to
. Stop the frequency converter
before making changes to open- and closed
loop functions
Required to use emergency mode.
0-11 Edit Set-up
Option:
Function:
Editing can either follow the active setup
selection (
), or be
fixed at a setup number. This parameter is
unique for LCP and buses.
[0]
Factory setup
[1]
*
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up
0-12 This Set-up Linked to
Option:
Function:
This parameter sets the AFE to automatically
synchronise the values of the 'not changeable
during operation' parameters between this set-
up and the set-up selected in this parameter.
Note: The values in this setup are overwritten.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Range:
Function:
0
*
[0 -
255 ]
View a list of all the set-ups linked by means of
0-12 This Set-up Linked to
. The parameter has one
index for each parameter set-up. The parameter
value displayed for each index represents which
set-ups are linked to that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 6.2 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Edit Set-ups / Channel
Range:
Function:
0
*
[-2147483648 -
2147483647 ]
View the setting of
0-11 Edit Set-up
for
each of the 4 different communication
channels. When the number is displayed
as a hex number, as it is in the LCP, each
number represents one channel.
Numbers 1-4 represent a set-up number;
‘F’ means factory setting; and ‘A’ means
active set-up. The channels are, from right
to left: LCP, FC-bus, USB, HPFB1-5.
Example: The number AAAAAA21h means
that the FC bus selected Set-up 2 in
0-11 Edit Set-up
, the LCP selected Set-up 1
and all others used the active set-up.
How to Programme
Operating Instructions
44