Group 600 -- Service and Diagnostics
600 Operation Data (OPERATION)
Value:
★
0
Total number of operating hours (TOT.HRS xxxx.x) *)
1
Running hours (RUN.HRS xxxx.x)*)
2
kWh (ENERGY xxxx.x)
3
Number of power ups (POW.UPS xxxxx)
4
Number of overheatings (OV.TEMP xxxxx)
5
Number of overvoltages (OV.VOLT xxxxx)
Function:
[Index 000.00-005.00]
Display of the selected operation data.
Description of choice:
Display range:
Total number of operating hours, running hours, and kWh is
0.0 to 99,999 (below 10,000, with 1 decimal).
Number of power ups, number of overheatings, and number
of overvoltages is 0 to 99,999.
Total number of operating hours, running hours, and kWh is
automatically reset after manual initialization. kWh can be
reset via parameter 011. Running hours can be reset via
parameter 012.
NOTE:
The data stated are saved every 8 hours. Number
of power ups, number of overheatings, and number
of overvoltages are saved as they occur.
601 Data Log (DATALOG)
0
1
2
3
4
- -19
Digital inputs
(DIG.IN) [0]
Control word
(CONTRL)[1]
Status word
(STATUS) [2]
Reference %
(REF. %) [3]
Frequency out
(F-OUT) [4]
Phase current
(IPHASE) [5]
DC voltage
(UDC)
[6]
Function:
[Index 000.00 - 019.06]
Log data for the last 3.2 seconds of operation before a stop
or a fault. The “+” and “-” keys can be used to cycle through
the display values and the 20 saved data sets. The data set
number is displayed on the far right of the display’s third
line.
Description of choice:
Digital inputs are stated in hex code
(0-FF).
Control words are stated as a hex code
(0-FFFF) for bus operation RS 485.
Status words are stated as a hex code
(0-FFFF) for bus operation RS 485.
Reference is the control signal in percent (0 to 100%).
Frequency out is the output frequency of the drive in Hz
(0.0 to 999.9).
Phase current is the output current in A (0.0 to 999.9).
DC voltage indicates the voltage of the drive’s DC bus in V
DC (0 to 999).
Twenty logged values are saved (0 to 19). The lowest num-
ber (0) contains the most recent/last data value saved, the
highest log number (19) contains the oldest data value.
Data values log every 160 msec. as long as the start signal
is active. The data log contains the 20 last log values
(approx. 3.2 sec.) before a stop signal is given (start not ac-
tive), or a trip occurs. It is possible to scroll through the log
values.
NOTE:
The data log is reset during power up.