VLT
®
Series 3500
57
★
= ROM default setting.
✔
= Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
Parameter Groups
Group 0 -- Operation and Display
Group 0 includes parameters that pertain to display
readouts, local operation and the handling of setups.
Group 0 parameters are:
000 Language Select
008 Local Loc/Hand (En/Dis)
001 Setup Selection
009 Local Rem/Auto (En/Dis)
002 Setup Copy
010 Local Ref (En/Dis)
003 Local/Remote (HOA)
011 Reset kWh Counter
004 Local Reference
012 Reset Time Counter
005 User Read-Out at Max
014 Power-up Mode
006 Local Reset (En/Dis)
015 Setup Program
007 Local Stop (En/Dis)
Group 1 -- Load and Motor
Group 1 includes parameters that tune the drive to the
application and the motor. Many of the special features of
the VLT 3500 Series drive are included in Group 1. One
of these is the “Automatic Energy Optimizer” (AEO),
which, if enabled, monitors the load characteristics during
operation and, if possible, reduces voltage to increase
efficiency. In addition, programming the correct variable
torque load characteristics is done in Group 1. The VLT
3500 Series has an integral controller with feed-forward
function. It is programmed in Group 1.
Group 1 parameters are:
100 Load Type (4)
116 Display @ Max Fdbk
101 Speed Control (Fdbk) (4) 117 Display Unit
102 Current Limit Control
119 Feed Forward Factor (4)
103 Motor Power (kW) (4)
120 Controller Range (4)
104 Motor Voltage (4)
121 Proportional Gain (4)
105 Motor Frequency (4)
122 Integral Time (4)
107 Motor Current (4)
123 Differentiation Time (4)
109 Starting Voltage (4)
124 Low Pass Filter (4)
114 Feedback Type
125 Feedback Factor (4)
115 Display @ Min Fdbk
Group 2 -- References and Limits
Group 2 includes parameters that establish operating
conditions and limits for the drive.
Group 2 parameters are:
201 Min. Freq. (Follower) (4)
214 Ramp Type (4)
202 Max. Freq. (Follower) (4) 215 Ramp-up Time (4)
203 Jog Freq. (4)
216 Ramp-down Time (4)
204 Dig. Ref. Type (Effect) (4) 217 Alt. Ramp-up Time (4)
205 Dig. Ref. 1 (%) (4)
218 Alt. Ramp-down Time (4)
206 Dig. Ref. 2 (%) (4)
219 Freq. Bypass 1 (4)
207 Dig. Ref. 3 (%) (4)
220 Freq. Bypass 2 (4)
208 Dig. Ref. 4 (%) (4)
221 Freq. Bypass 3 (4)
209 Current Limit (A) (4)
222 Freq. Bypass 4 (4)
210 Warn. Freq. Low (4)
223 Freq. Bypass Wdth % (4)
211 Warn. Freq. High (4)
224 Carrier Freq. (4)
212 Warn. Curr. Low (4)
225 Variable Carrier Freq. (4)
213 Warn. Curr. High (4)
232 Idle Running Current (4)
Group 3 -- Functions and Timers
Group 3 includes parameters that establish stop/start
conditions and time delays for the drive.
Group 3 parameters are:
301 Start Freq. (4)
310 Trip Delay, Current Limit
302 Start Delay (4)
311 Trip Delay, Inv. Fault
303 High Starting Torque (4)
312 Max Auto Restart Time
304 Mains Failure (Stop)
313 Motor Check (4)
305 Flying Start (4)
314 Motor Preheat (4)
306 DC Braking Time (4)
315 Motor Therm. Protect (4)
308 DC Brake Voltage (4)
316 Relay 1 ON Delay
309 Reset mode (Counts)
317 Relay 1 OFF Delay
Group 4 -- Inputs and Outputs
Group 4 includes parameters that allow the drive to
respond to inputs and send outputs to other devices.
Group 4 parameters are:
400 Binary Input 16
409 Relay Output 01
401 Binary Input 17
410 Relay Output 04 (4)
402 Binary Input 18
411 Analog Ref. Type (4)
403 Binary Input 19
412 Term. 53 Input Voltage
404 Binary Input 27 (Stop)
413 Term. 54 Input Voltage
405 Binary Input 29
414 Time Out
406 Binary Input 32/33
415 Time Out Function
407 Signal Output 42 (4)
420 Ext. Hand Ref. Type
408 Signal Output 45
Group 5 -- Serial Communication
Group 5 includes parameters that allow the drive to
respond to serial communication.
Group 5 parameters are:
500 Address
509 Setup Select
501 Baud Rate
510 Digital Speed Select
502 Data Readout
511 Bus Jogging 1
503 Coasting
512 Bus Jogging 2
504 Q-stop
513 Catch Up Value
505 DC Brake
514 Bus Bit 4
506 Start
515 Bus Bit 11/12
507 Direction
516 Bus Reference
508 Reset
517 Store Data Values
Group 6 -- Service and Diagnostics
Group 6 includes parameters that help diagnose
operation and service problems.
Group 6 parameters are:
600 Operation Data
604 Operation Mode
601 Data Log
605 Personal Display Select
602 Fault Memory
606 Display Mode
603 Type Plate
650 VLT Type
(4) This parameter can be set differently in each of the
four parameter sets.