= ROM default setting.
✔
= Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
605 Dual Function Display Select (DISPLAY SE)
Value:
★
Standard display (STANDARD DISP)
[0]
Reference % (REFERENCE %)
[1]
Frequency Hz (FREQUENCY Hz)
[2]
Feedback unit (FEEDBK 'UNIT')
[3]
Current A (CURRENT A)
[4]
Torque % (TORQUE %)
[5]
Power kW (POWER kW)
[6]
HP power (POWER HP)
[7]
Energy kWh (ENERGY kWh)
[8]
Output voltage V (OUTPUT VOLT.V)
[9]
DC voltage (DC BUS V)
[10]
VLT therm % (ETR (VLT) %)
[11]
Motor therm % (ETR (MOT) %)
[12]
Running hours (RUN HOURS)
[13]
Input status “binary code” (DIGITAL INPUT) [14]
Function:
The display can show two data values at the same time.
The value chosen here is shown in line 2 on the display.
Description of choice:
Standard display [0] is chosen if normal reading is desired.
For example, when Hz is shown in line 1, line 2 will show
“Frequency” and the operating mode will be shown in line 3.
Dual function display select. One of the other fourteen data
values above is selected if a different operating value is to
be displayed in line 2. For example frequency can be
shown in line 1 and current shown in line 2 at the same
time.
NOTE:
To view both lines at the same time, the display
must be in Display mode. To enter the Display
mode from any other mode, press “Menu” and
“Data” simultaneously.
606 Display Mode (DISPLAY MO)
Value:
★
Standard display (QUICK DISPLAY)
[0]
Extended display (EXT. DISPLAY)
[1]
Function:
Choose between two different Display Modes. Extended
display allows the operator to cycle through a wide range of
data types. See the section on Display Mode.
650 VLT Type (VLT TYPE)
Function:
Used for indicating the unit in which the control card is
placed, in cases where the control card is not able to deter-
mine this itself. Or used for choosing the voltage range in
multi-voltage units whose factory setting varies from that re-
quired.
Description of choice:
This parameter is used for choosing the right VLT
type/size/voltage. The power board will identify itself to the
control, and in most cases the proper type/size/voltage will
automatically be selected when power is applied to the
drive.
VLT Types 3575 through 3800 are multi-voltage units. It is
important that the line voltage be set correctly by this pa-
rameter. If the factory-set voltage does not correspond to
the line voltage of the application for which the unit is in-
tended, proceed as follows:
1) Select the desired VLT type/size/voltage.
2) Select parameter 604, data value initialization.
3) Remove AC power and wait for the light in the display to
go out.
4) Reapply AC power.
NOTE:
When reapplying power, check the display to see
that the new data is shown.