Drive Setup
When the drive is first powered up, the items in the Quick
Setup menu should be viewed and changed as required.
The Quick Setup menu items are shown below. If
preferred, these items can be viewed and changed from
the Extended menu.
Quick setup no.
Extended menu
Designation
Settings
Data Entry
0
000
Language
Choose from six languages
Choose English (typical)
1
104
Motor voltage
Check nameplate on motor
Enter line voltage 460 (typical)
2
107
Motor current
Check nameplate on motor
Enter FLA motor amps
3
105
Motor frequency
Check nameplate on motor
Enter 60 Hz (typical)
4
412
Speed reference
Select reference range
Choose 0 to 10 V DC (typical)
5
413
Speed reference
Select reference range
Choose 4 to 20 mA (typical)
6
201
Min. frequency
Select desired frequency
Enter 20 Hz (typical)
7
202
Max. frequency
Select desired frequency
Enter 60 Hz (typical)
8
215
Ramp up
Select desired time
Enter 30 sec (typical)
9
216
Ramp down
Select desired time
Enter 30 sec (typical)
Return to Factory Defaults
It is possible to globally return all parameters to the
factory default settings. If undocumented changes have
been made to the settings and the drive is not responding
as it should, it is possible to start over.
Returning to the factory defaults may affect all
parameters. Be sure to review all parameters for desired
settings after returning to the factory defaults.
There are three ways to return to factory defaults.
1. One way initializes the EEPROM and therefore resets
everything. To do this, first remove power from the
drive. Then press and hold the “Menu”, “Data” and
“Local/Hand” keys while reapplying power. Release
the keys after the third line in the display reads “init
eeprom”.
2. If you wish to retain the settings of parameters 501
(PC communication), 821, 822, 904 and 918 (Profibus
communication), the cumulative kWh and total running
hours, use Parameter 604 to reset to factory settings
instead. See parameter 604. Set it to INITIALIZE [3] .
3. It is also possible to return the parameter sets to the
factory defaults one set at a time or all at once. If
multiple settings are used, it may be desirable to
change only one of them, or change them one at a
time. Use the procedure for parameter 001 and
parameter 002 to copy the factory defaults to a single
parameter set or to all four parameter sets.
Lockout
Unwanted programming can be prevented by opening
switch pin 01 on the control card. When the switch pin is
open, changes cannot be made to the programming. The
Local/Hand, Stop/Reset, Remote/Auto, and Start keys
are functional, but the programming keys are not. “LOCK
OPEN” is displaced on the third line of the display when
programming changes are attempted with the switch pin
open.
Control functions can be locked
out individually. See
parameter 006 through 010.