VLT
®
Series 3500
83
410 Terminal 04 Relay Output (RELAY 04)
Value:
Control ready (CONTROL READY)
[0]
Unit ready (UNIT READY)
[1]
Ready - remote control (UNT RDY RCTL)
[2]
Enabled (ENABLED noWR)
[3]
★
Running (RUNNING)
[4]
Running, no warning (RUNNING noWR)
[5]
Running in range, no warning (RUNinRANGE)
[6]
Speed = reference, no warning (RUN@REF noWR) [7]
Alarm (ALARM)
[8]
Alarm or warning (ALARM or WARN)
[9]
Current limit (CURRENT LIMIT)
[10]
Out of frequency range (OUT FREQ RGE)
[11]
Warning of F low (LO FREQ. WARN)
[12]
Warning of F high (HI FREQ. WARN)
[13]
Out of current range (OUT CURR RGE)
[14]
Warning of I low (LO CURR. WARN)
[15]
Warning of I high (HI CURR. WARN)
[16]
Motor thermal overload (MOT.THERM.WARN)
[17]
Ready and no motor thermal overload
(READY+MOT.OK)
[18]
Ready and remote control (RDY+MOT+REM)
[19]
Ready and no over-/undervoltage (RDY+DC V OK) [20]
Idle running current (NO LOAD CURR)
[21]
Function:
Relay outputs 01 and 04 can be used for indicating status
and warnings.
The relay is activated when the conditions for the different
data values are fulfilled. When relay 4 is activated, there is
a connection between terminals 4 and 5.
Description of choice:
[0]-[16] See explanations under parameter 407.
[17]-[21] See explanations under parameter 409.
411 Analog Reference Type (ANALOG REFTYPE)
Value:
★
Linear between minimum and maximum (LINEAR)
[0]
Proportional with lower limit (PROP W/MIN.)
[1]
Function:
It is possible to select different forms of how the output fre-
quency is to depend on the analog reference signal.
Description of choice:
Used for deciding how the drive is to follow an analog refer-
ence signal, see graphs in next column.
Ou
tpu
t Spee
d
Speed Reference Signal
Min.
(parameter 201)
Max.
(parameter 202)
Min.
0 V
4 mA
0 mA
Max.
10 V
20 mA
20 mA
★
= ROM default setting.
✔
= Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
Output Speed
Speed Reference Signal
Min.
(parameter 201)
Max.
(parameter 202)
Min.
0 V
4 mA
0 mA
Max.
10 V
20 mA
20 mA
Choice [0]
Choice [1]
412 Terminal 53 Analog Input Voltage
(INPUT #53)
Value:
✔
No operation (NO OPERATION)
[0]
★
0 to 10 V (0 to 10 V DC)
[1]
10 to 0 V (10 to 0 V DC)
[2]
2 to 10 V (2 to 10 V DC)
[3]
10 to 2 V (10 to 2 V DC)
[4]
1 to 5 V (1 to 5 V DC)
[5]
5 to 1 V (5 to 1 V DC)
[6]