![Danfoss VLT 3500 Series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/danfoss/vlt-3500-series/vlt-3500-series_instruction-manual_3610382050.webp)
VLT
®
Series 3500
48
Combinations of Control Panel Keys
MENU AND DATA KEYS If these keys
are pressed simultaneously, the
system switches to Display mode from
any other mode.
MENU AND + KEYS If these keys are
pressed simultaneously, the system
switches to Extended Menu from any
mode.
MENU AND - KEYS If these keys are
pressed simultaneously, the system
switches to the Quick Set Up Menu
from any mode.
MENU, DATA and LOCAL/HAND
If these keys are pressed and held
while power is applied to the drive,
all of the drive’s parameters and
history logs will be reset. These
three buttons must be held until the
third line of the display shows “init
eeprom”.
STOP/RESET Holding down Stop/Reset while
pressing other keys allows access to the
function of the other keys when a drive fault
would otherwise have made the other key
inactive.
Functions of the Keys
The eight keys on the control
panel of the drive are used for
programming as follows:
MENU KEY Press this key to toggle from
Display mode to Quick Setup mode. This key
is also used for switching from Data mode to
Menu mode.
DATA KEY Press this key to toggle from Menu
mode to Data mode or Display mode. This key
is also used for moving the cursor between the
decimal places of numerical data values. The
program automatically leaves Data mode after
20 seconds if no operation is registered.
+ KEY AND - KEY These keys are used for
scrolling through the different Menu Modes
and their parameters and for choosing a
specific parameter value or for scrolling
parameter data. They are also used for
changing the speed when in Local mode.
LOCAL/HAND KEY This key is used for
selecting local operation. This key can be
deactivated by using parameter 008.
REMOTE/AUTO KEY This key is used for
selecting remote operation. This key can
deactivated by using parameter 009.
STOP/RESET KEY This key is used to stop
the drive and for resetting if a trip occurs. The
top line of the display flashes when the drive
has been stopped using this key. The start key
must then be pressed to restart the drive. The
reset function of this key can be deactivated
using parameter 006. The stop function of this
key can be deactivated using parameter 007.
START KEY This key is used for starting the
drive. If the drive has been stopped using the
Stop/Reset key, the Start key must be pressed
to restart the drive.