![Danfoss VLT 3500 Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/danfoss/vlt-3500-series/vlt-3500-series_instruction-manual_3610382009.webp)
7
VLT type
3502
3504
3506
3508
3511
3516
3522
3532
3542
3552
3562
Output current
I
VLT,N
[A]
2.6
4.8
8.2
12.6
14.4
21.7
37.9
41.4
54.0
65.0
78.0
I
VLT, MAX
(60 s) [A]
2.9
5.3
9.0
13.9
15.9
24.0
30.7
45.8
59.6
71.5
85.8
Output
S
VLT, N
[kVA]
1.6
4.1
7.1
9.6
12.4
18.8
24.2
35.9
46.8
56.3
67.5
Typical shaft output
P
VLT, N
[HP]
1
3
5
7.5
10
15
20
30
40
50
60
Max. cable cross-section
[AWG]
12
12
12
12
6
6
6
6
4
4
4
Max. motor cable length
[feet]
1000 (unshielded)*
Output voltage
V
M
[%]
1-100, of AC line voltage
Output frequency
f
M
[Hz]
0-120
Rated motor voltage
V
M, N
[V]
440/460/500
Rated motor frequency
f
M, N
[Hz]
50/60/87/100
Thermal protection during operation
Integrated thermal motor protection (electronic); thermistor to DIN44081
Switching on output
Unlimited (frequent switching may cause cut-out)
Ramp times
[s]
0.1-3600
VLT type
3502
3504
3506
3508
3511
3516
3522
3532
3542
3552
3562
Max. input current
I
L, N
[A]
2.6
4.8
8.2
11.1
14.4
19.6
26.0
34.8
48.6
53.0
72.0
Max. cable cross-section
[AWG]
12
12
12
12
6
6
6
6
4
4
4
Max. pre-fuses
[A]
20
20
25
25
30
30
40
50
60
100
125
Supply voltage
[V]
3 phase, 440/460/500
±
10% (VDE 0160)
Supply frequency
[Hz]
50/60
Power factor / cos
0.9/1.0
Efficiency
0.96 at 100% load
Switching on input
times/min.
2
Radio noise, cable borne
VLT type 3502-08: EN 55011, class A, gr. 1, with option class B. gr 1
(with shielded cables)
VLT type 3516-62 with option: EN 55011, cl. A, 1 VDE 0875, part 3, curve N
VLT type
3502
3504
3506
3508
3511
3516
3522
3532
3542
3552
3562
Weight (lbs)
Chassis (IP00)
16
16
26
31
31
–
–
–
–
–
–
and
NEMA 1 (IP 20)
–
–
–
–
–
55
57
68
108
119
119
enclosure type
NEMA 1 (IP 21)
18
18
29
33
33
–
–
–
–
–
–
NEMA 12 (IP 54)
24
24
31
33
33
75
81
106
139
152
152
Power loss at max. load
[W]
60
130
160
200
240
281
369
880
1133
1440
1888
Vibration test
[g]
0.7
Relative humidity
[%]
VDE 0160 5.2.1.2.
Ambient temperature
[
°
C]
–10
➔
+40, operation at full load
1)
–30/25
➔
+65/70, storage/transport
Adjustable frequency drive protection
Protection against grounding and short-circuiting
EMC standards
Emission
EN 50011, VDE 0875 part 3
Immunity EN 50082-2, IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5, VDE 0160, SEN 361503
* If shielded cable is to be used, consult Danfoss for cable length.
1) In the range –10 to 0
°
C, the equipment can start and run; however, the display values and certain operating characteristics will
not fulfill the specifications.
VLT
®
Series 3500
3 Phase, 440/460/500 Volt, Units