VLT
®
Series 3500
60
★
= ROM default setting.
✔
= Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
009 Remote/Auto (KEY REMOT/)
Value:
Disable (DISABLE)
[0]
★
Enable (ENABLE)
[1]
Function:
Allows, or prevents, the drive from being switched to the
“Remote/Auto” mode from the keypad.
010 Local Speed Selection (LOC REFERE)
Value:
Disable (DISABLE)
[0]
★
Enable (ENABLE)
[1]
Function:
The ability to change the local speed reference via param-
eter 004 can be enabled or disabled.
Description of choice:
If
disable [0] is selected in parameter 010, the local speed
reference cannot be changed via parameter 004.
011 Reset of kWh (ENERGY COU)
Value:
★
No reset (NO RESET)
Reset (RESET)
Function:
Zeroing of kW energy counter.
Description of choice:
Reset is initiated when RESET has been selected and the
Data mode is exited. Cannot be selected via the serial bus.
CAUTION When RESET has been selected, zeroing has
been completed.
012 Reset of Hours Run (HOUR COUNT)
Value:
★
No reset (NO RESET)
Reset (RESET)
Function:
Resets the hour meter to zero. (See also parameter 600).
The hour meter functions only when a start command has
been given.
Description of choice:
Reset starts when Data mode is exited. The hour meter
cannot be reset via the serial bus.
014 Power Up Mode (POWER-UP M)
Value:
✔
Auto restart in local operation, using
saved reference speed (AUTO RESTART)
[0]
★
Stopped in local operation, using
saved reference speed (LOC=STOP)
[1]
Stopped in local operation, set speed reference to 0
(LOC=STP+REF=0)
[2]
Function:
When the “Local/Hand” key has been activated and the
drive is running with local speed reference, or if FREEZE
REFERENCE is used, it is possible to program the state in
which the drive is to start up after AC power has been lost
and restored.
Description of choice:
Auto restart in local operation, use saved reference speed
[0] is selected if the unit is to start up with the local speed
reference that was in force when AC power was lost.
Stopped in local operation, use saved reference [1] is se-
lected if the unit is to remain stopped when the AC line is
restored. After the “Start” key is pressed, the saved, local
speed reference is used.
Stopped in local operation, set speed reference to 0 [2] is
selected if the unit is to remain stopped when the AC line is
connected. Local Reference (parameter 004) and Freeze
Reference (parameter 400, 401 or 405) are reset to 0.
If remote operation is used with a Freeze Reference func-
tion the Freeze Reference will be reset to 0 when the AC
power is removed and restored. Use parameter 406 to re-
tain the Freeze Reference speed through a power outage.
NOTE:
In remote-controlled operation, the restart function
is always an “Auto Restart”. If the unit is to remain
stopped after power is restored, select Pulse Start
in parameter 402.