= ROM default setting.
✔
= Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
407 Terminal 42 Output (OUTPUT 42)
Value:
Control ready (CONTROL READY)
[0]
Unit ready (UNIT READY)
[1]
Ready - remote control (UNT RDY RCTL)
[2]
Enabled (ENABLED noWR)
[3]
Running (RUNNING)
[4]
Running, no warning (RUNNING noWR)
[5]
Running in range, no warning (RUNinRANGE)
[6]
Speed = reference, no warning
(RUN@REF noWR)
[7]
Alarm (ALARM)
[8]
Alarm or warning (ALARM or WARN)
[9]
Current limit (CURRENT LIMIT)
[10]
Out of frequency range (OUT FREQ RGE)
[11]
Warning of low freq.(LO FREQ. WARN)
[12]
Warning of high freq.(HI FREQ. WARN)
[13]
Out of current range (OUT CURR RGE)
[14]
Warning of low current (LO CURR. WARN)
[15]
Warning of high current (HI CURR. WARN)
[16]
0 to 100 Hz
0 to 20 mA(100 Hz 0 to 20 mA)
[17]
0 to 100 Hz
4 to 20 mA(100 Hz 4 to 20 mA)
[18]
0 to f
MAX
0 to 20 mA(Fmax 0 to 20 mA)
[19]
0 to f
MAX
4 to 20 mA (Fmax 4 to 20 mA)
[20]
REF
MIN
to REF
MAX
0 to 20 mA(REFmax 0 to 20 mA) [21]
REF
MIN
to REF
MAX
4 to 20 mA(REFmax 4 to 20 mA) [22]
FB
MIN
to FB
MAX
0 to 20 mA(FBmax 0 to 20 mA) [23]
FB
MIN
to FB
MAX
4 to 20 mA(FBmax 4 to 20 mA) [24]
★
0 to I
MAX
0 to 20 mA(CURmax 0 to 20 mA) [25]
✔
0 to I
MAX
4 to 20 mA(CURmax 4 to 20 mA) [26]
0 to I
LIM
0 to 20 mA(CURlim 0 to 20 mA) [27]
0 to I
LIM
4 to 20 mA(CURlim 4 to 20 mA) [28]
0 to kW
MAX
0 to 20 mA(PWRlim 0 to 20 mA) [29]
0 to kW
MAX
4 to20 mA(PWRlim 4 to 20 mA) [30]
Function:
Terminals 42 and 45 can be programmed to give one of
these output signals: 24 V DC, (max. 40 mA); 0 to 20 mA;
or 4 to 20 mA.
The 24 V signal is used to report the status of a selected
drive status. The 0 to 20 mA and 4 to 20 mA outputs are
used for analog readouts.
Description of choice:
[0]
VLT is ready for use.
[1]
VLT is ready for use.
[2]
VLT is in the remote mode and is ready for use.
[3]
VLT is ready, there are no warnings.
[4]
VLT is running (output frequency is > 0.5 Hz or has
a start signal).
[5]
VLT is running (output frequency is > 0.5 Hz or has
a start signal), there are no warnings.
[6]
VLT is running within the programmed frequency
and/or current range, there are no warnings.
[7]
VLT output frequency corresponds to the reference,
there are no warnings.
[8]
There is an alarm.
[9]
There is a warning.
[10]
The current limit set in parameter 209 has been ex-
ceeded.
[11]
The motor is running out of the frequency range pro-
grammed in parameters 210 and 211.
[12]
The motor is running below the frequency pro-
grammed in
parameter 210.
[13]
The motor is running above the frequency pro-
grammed in
parameter 211.
[14]
The motor is running out of the current range pro-
grammed in
parameters 212 and 213.
[15]
The motor current is below the current programmed
in parameter 212.
[16]
The motor current is above the current programmed
in parameter 213.
[17- 18] The output signal represents the drive’s speed, 20
mA represents an output frequency of 100 Hz. The
minimum signal represents 0 Hz.
[19-20] The output signal represents the drive’s speed. 20
mA represents the frequency set in parameter 202.
The minimum signal represents 0 Hz.
[21-22] The output signal represents the total speed refer-
ence signal supplied to the drive from the three ex-
ternal inputs (set by parameters 401, 412, and 413)
and the bus reference (set by parameter 516). 20
mA represents the maximum speed reference sig-
nal and the minimum signal represents the mini-
mum speed reference signal. The drive does not
have to be running to display this reference signal.
[23-24] The output signal represents the feedback signal ap-
plied to terminal 17, 53 or 60, as setup by param-
eters 401, 412 or 413.
[25-26] The output signal represents the output current from
the drive. The maximum signal represents 110% of
the drive’s rated output current. The minimum sig-
nal represents no output current.
[27-28] The output signal represents the output current from
the drive. The maximum signal represents the cur-
rent limit value, set in parameter 208.
[29-30] The output signal represents the output power from
the drive. The maximum signal represents the
motor’s rated power, which was entered in param-
eter 103.