![Danfoss VLT 3500 Series Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/danfoss/vlt-3500-series/vlt-3500-series_instruction-manual_3610382060.webp)
VLT
®
Series 3500
58
★
= ROM default setting.
✔
= Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
Function:
This parameter chooses the setup number you want to con-
trol the drive.
Description of choice:
Pre-programmed [0] contains the default parameters. The
parameters in this setup cannot be changed. It can be used
to restore the default parameters to one or more of the
numbered setups. Use parameter 002 to copy these de-
faults to one or more of the numbered setups.
Setups 1-4 [1]-[4] are four individual setups for use as de-
sired. Changes can only be made to the setup specified in
parameter 015. By default, this is the currently active setup,
which is specified here. Changes made to the active setup
take effect immediately. Certain parameters require that the
drive be stopped before any change can be made. The third
line of the display will indicate this.
Multi setup [5] is used if remote switching from one setup to
another is required. The parameters that can be different
from one setup to another are shown in the general de-
scription of the groups. If you want to change from one
setup to another remotely, choose “Multi-setup” and use
terminals 16/17 or 32/33, or the serial port to make the
change. See parameter 400, 401 and 406.
002 Copy of Setups
(
(MENU SET C)
Value
★
No copying (DO NOT COPY)
[0]
Copy to 1 from # (COPY TO 1 FRO)
[1]
Copy to 2 from # (COPY TO 2 FRO)
[2]
Copy to 3 from # (COPY TO 3 FRO)
[3]
Copy to 4 from # (COPY TO 4 FRO)
[4]
Copy to ALL from # (COPY ALL FROM)
[5]
Function:
A menu setup can be copied to one of the other setups or to
all the other setups simultaneously, although not to setup [0].
Only the setup chosen in parameter 015 can be used as
the source for the copying.
Copying is only enabled in Stop mode.
Description of choice:
The copying starts when you have entered the desired
copying function and Data mode is left by pressing the
“Menu” key, or after 20 seconds of no activity. Line 3 in the
display flashes while copying is in progress. The display in-
dicates the destination setup and the source setup. The
source is always the setup specified in parameter 15. When
copying has been completed, the data value shifts auto-
matically to
No copying [0].
Programming
Below is the detail for all the parameters for all of the
groups. You may view the present setting and change the
setting by using the key pad on the drive. Many parameters
can also be read and changed using the computer-based
VLS-DIALOG program. The following description assumes
that the key pad is being used, but the parameters and their
function are the same either way.
Before changing any parameter, it is recommended that
you write down the present setting. This will allow resetting
the parameter if the change does not result in the desired
performance.
To enter the extended menus to change a parameter:
1. Press “Menu” and “+” simultaneously.
2. Press “+” or “-” to move to desired group.
3. Press “Menu” to allow access to the items in the
group.
4. Press “+” or “-” to move to the desired item and view
the present value for that item.
5. Press “Data” to access the bottom line of the display
to allow changing the present selection.
6. Press “+” or “-” to scroll through the possible values.
7. Press “Menu” and “Data” simultaneously to leave the
programming mode.
Group 0 -- Operation and Display
000 Language (LANGUAGE)
Value:
★
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPANOL)
[4]
Italian (ITALIANO)
[5]
Function and Description of choice:
Determines the language of the display. This can also be
chosen from Quick Set Up step 0.
001 Setup Choice, Operation (SETUP OPER)
Value:
Pre-programmed (FACTORY SET)
[0]
★
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
Multi-setup (MULTI SETUP)
[5]