background image

User 

Guide RS8GD602 © Danfoss 2015-10 

Optyma 

Plus 

TM

Survey of functions

Function

Para- 

meter

Parameter by operation via data 

communication

Normal display

The display shows the temperature value for the suction pressure Ts or from the con-

densing pressure Tc. Enter which of the two are to be displayed in o17.

During operation, when one of the two is shown in the display, the other value can be 

seen by pressing and holding in the lower button.

Ts / Tc

Thermostat

Thermostat control

Set point

The controller's reference Tc is the outside tempe set point + any applicable 

offset. 

Enter the set point by pressing the middle button. A offset can be entered in r13.

Reference

Unit

Set here if the display is to show SI-units or US-units

0: SI (°C and bar)

1: US (°F and Psig).

r05

Unit 

°C=0. / °F=1

(Only °C on AKM, whatever the set-

ting)

Start / stop of refrigeration

With this setting refrigeration can be started, stopped or a manual override of the 

outputs can be allowed. (For manual control the value is set at -1. Then the relay out-

lets can be force-controlled by the respective reading parameters (u58, u59 etc.). Here 

the read value can be overwritten.)

Start / stop of refrigeration can also be accomplished with the external switch func-

tion connected to a DI input.

If the external switch function is deselected, the input must be shorted.

Stopped refrigeration will give a ”Standby alarm”.

r12

Main Switch

1: Start

0: Stop

-1: Manual control of outputs allowed

Night setback value

The controller reference is raised by this value when the controller switches to night 

operation. 

r13

Night offset

Reference Ts

Here the reference is entered for the suction pressure Ts in degrees.

r23

Ts Ref

Reference Tc

Here the current controller reference for condensing pressure Tc can be read out in 

degrees.

r29

Tc Ref

Minimum condensing temperature 

(lowest permitted regulation reference)

Here the lowest permitted reference is entered for the condensing temperature Tc.

r82

MinCondTemp

Maximum condensing temperature

 (highest permitted regulation reference)

Here the highest permitted reference is entered for the condensing temperature Tc.

r83

MaxCondTemp

Maximum discharge  gas temperature

Here the highest permitted discharge gas temperature is entered. The temperature 

is measured by sensor Td. If the temperature is exceeded, the fan will be started at 

100%. A timer is also started which can be set in c72. If the timer setting runs out, 

the compressor will be stopped and an alarm will be issued. The compressor will be 

reconnected 10 K below the cut-out limit, but only after the compressor's off timer 

has expired.

r84

MaxDischTemp

Night setbck

(start of night signal.  0=Day, 1=Night)

Alarm

Alarm settings

The controller can give alarm in different situations. When there is an alarm all the 

light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay 

will cut in.

With data communication the impor-

tance of the individual alarms can be 

defined. Setting is carried out in the 

“Alarm destinations” menu via AKM. 

Delay of a DI2 alarm

 

A cut-out/cut-in input will result in alarm when the time delay has been passed. The 

function is defined in o37

A28

AI.Delay DI2

High condensing temperature

The limit value (difference over normal reference) to which the condensing tempera-

ture has increased, and at which an alarm must be issued. Can be set in K.

A70

Air flowDiff

Delay time for alarm A70. Set in minutes.

A71

Air flow del
Reset alarm
Ctrl. Error

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: