background image

Optyma Plus 

TM 

User 

Guide RS8GD602 © Danfoss 2015-10 

13

Light-emitting diodes (LED) on front panel

The LED’s on the front panel will light up when the relevant relay 

is activated.

 = Refrigeration

 = heating element in crankcase is on

 = 

 Fan running

The light-emitting diodes will flash when there is an alarm.

In this situation you can download the error code to the display 

and cancel/sign for the alarm by giving the upper button a brief 

push.

The buttons

When you want to change a setting, the upper and the lower but-

ton will give you a higher or lower value depending on the button 

you are pushing. But before you change the value, you must have 

access to the menu. You obtain this by pushing the upper button 

for a couple of seconds - you will then enter the column with pa-

rameter codes. Find the parameter code you want to change and 

push the middle buttons until value for the parameter is shown. 

When you have changed the value, save the new value by once 

more pushing the middle button.

(If not operated for 20 (5) seconds, the display will change back to 

the Ts/Tc temperature display).

Examples

Set menu

1. Push the upper button until a parameter r05 is shown

2. Push the upper or the lower button and find that parameter you 

want to change

3. Push the middle button until the parameter value is shown

4. Push the upper or the lower button and select the new value

5. Push the middle button again to freeze the value.

Display

The values will be shown with three digits, and with a setting you 

can determine whether the temperature is to be shown in °C or in 

°F.

Operation

Get a good start

With the following procedure you can start regulation very quick-

ly:

1

 Open parameter r12 and stop the regulation (in a new and not 

previously set unit, r12 will already be set to 0 which means 

stopped regulation.  

Select refrigerant via parameter o30

3

 Open parameter r12 and start the regulation. Start/stop at input 

DI1 or DI2 must also be activated.

4

 Go through the survey of factory settings. Make any necessary 

changes in the respective parameters.

5

 For network. 

- Set the address in o03  

- Activate scan function in the system manager.

Note

When delivering the condensing unit, the controller will be set to 

the condensing unit type (setting o61). This setting will be com-

pared with your refrigerant setting. If you select a "non-permitted 

refrigerant", the display will show "ref" and await a new setting.

(In the event of a controller change, 061 must be set as indicated 

in the instructions from Danfoss)

Cutout alarm relay / receipt alarm/see alarm code 

• A short press of the upper button

If there are several alarm codes they are found in a rolling stack. 

Push the uppermost or lowermost button to scan the rolling 

stack.

Set point

1. Push the middle button until the temperature value is shown

2. Push the upper or the lower button and select the new value

3. Push the middle button again to conclude the setting.

Reading the temperature at Ts (if Tc is the primary display) or Tc (if Ts 

is the primary display)

• A short press of the lower button

Menu survey

SW = 3.0x

Parameter

Min.-value Max.-value

Factory 

setting

Actual 

setting

Function

Code

Normal operation

Set point (regulation reference follows the number of degrees above the outside temperature 

Tamb)

- - -

2.0 K

20.0 K

8.0 K

Regulation

Select SI or US display. 0=SI (bar and °C). 1=US (Psig and °F)

r05 

0/°C

1/F

0/°C

Internal Main Switch. Manual and service = - 1, Stop regulation = 0, Start regulation =1

r12 

-1

1

0

Offset during night operation. During night operation the reference is raised by this value

r13

0 K

10 K

2 K

Set point for suction pressure Ts 

r23

-25 °C

10°C

-7°C

Readout of reference for Tc

r29

-

-

-

-

Min. condensing temperature (lowest permitted Tc reference)

r82

0°C

40°C

10°C

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: