background image

16 

User 

Guide RS8GD602 © Danfoss 2015-10 

Optyma 

Plus 

TM

DI1

Digital input signal.

Used to start/stop cooling (room thermostat) 

Starts when the input is short-circuited.

DI2

Digital input signal.  

The defined function is active when the input is short-circuited/

opened. The function is defined in o37. 

Pc

Pressure transmitter, ratiometric AKS 32R, 0 to 32 bar

Connect to terminal 28, 29 and 30.

Ps

Pressure transmitter, ratiometric e.g.

 

AKS 32R, -1 to 12 bar

Connected to terminal 31, 32 and 33.

S2

Air sensor, Tamb. Pt 1000 ohm sensor, eg. AKS 11

S3

Discharge gas sensor, Td. Pt 1000 ohm sensor, eg. AKS 21

S4

Suction gas temperature, Ts. Pt 1000 ohm sensor, eg. AKS 11

S5, 

Extra temperature measurement, Taux. Pt 1000 ohm sensor, eg. AKS 11

S6, 

Extra temperature measurement, S6. Pt 1000 ohm sensor, eg. AKS 11

EKA Display

If there is be external reading/operation of the controller, display type 

EKA 163B or EKA 164B can be connected. 

RS485 (terminal 51, 52,53)

For data communication, but only if a data communication module is 

inserted in the controller. The module can be Lon.

If data communication is used, it is important that the installation of 

the data communication cable is performed correctly.

See separate literature No. RC8AC…

AO1, terminal 54, 55

Output signal, 0-10 V. Must be used if the fan is equipped with internal 

speed control and 0-10 V d.c. input, e.g. EC-motor.

AO2, terminal 56, 57

Output signal, 0-10 V. Must be used if the compressor is speed 

controlled.

MODBUS (terminal 60, 61, 62)

Built in Modbus data communication.

If data communication is used, it is important that the installation of 

the data communication cable is performed correctly.

See separate literature No. RC8AC…

(Alternatively the terminals can be connected to an external display 

type EKA 163A or 164A, but then they cannot be used for data 

communication. Any data communication must then be carried out 

by one of the other methods.)

Supply voltage

230 V a.c. (This must be the same phase for all 230 V connections).

FAN

Fan connection. Speed controlled internally.

Alarm

There is a connection between terminal 7 and 8 in alarm situations 

and when the controller is without power.

Comp

Compressor

There is a connection between terminal 10 and 11, when 

the compressor is running.

CCH

Heating element in the crankcase

There is connection between terminals 12 and 14 when heating takes 

place.

Fan

There is connection between terminals 15 and 16 when the fan's 

speed is raised to over 95%. (Fan signal changes from terminal 5-6 to 

15-16. Connect wire from terminal 16 to the fan.)

Aux

Liquid injection in suction line

There is connection between terminals 17 and 19, when the function 

is active.

DI3

Digital input signal from low/high pressure monitoring.  

The signal must have a voltage of 0 / 230 V AC. 

Electric noise

Cables for sensors, DI inputs and data communication 

must

 be kept 

separate from other electric cables:

- Use separate cable trays

- Keep a distance between cables of at least 10 cm.

- Long cables at the DI input should be avoided

Installation considerations

Accidental damage, poor installation, or site conditions, can give rise 

to malfunctions of the control system, and ultimately lead to a plant 

breakdown. Every possible safeguard is incorporated into our prod-

ucts to prevent this. However, a wrong installation, for example, could 

still present problems. Electronic controls are no substitute for normal, 

good engineering practice.
Danfoss will not be responsible for any goods, or plant components, 

damaged as a result of the above defects. It is the installer's respon-

sibility to check the installation thoroughly, and to fit the necessary 

safety devices. Special reference is made to the necessity of signals 

to the controller when the compressor is stopped and to the need of 

liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further advice, 

etc. 

Connections

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: