background image

User 

Guide RS8GD602 © Danfoss 2015-10 

Optyma 

Plus 

TM

Integration Time Tn

If the Tn value is increased, the fan speed will change.

n05

Tn sec

Amplification factor Kp max

The regulation uses this Kp, when the measured value is far from reference 

n95

Cmp kp Max

Fan speed

The actual fan speed is read out here as a % of nominal speed.

F07

Fan Speed %

Change in fan speed

A permitted change in fan speed can be entered for when the fan speed is to be low-

ered. The setting can be entered as a percentage value per second.

F14

DownSlope

Jog speed

Set the fan's start-up speed here. After ten seconds the function jog function will stop 

and the fan speed will then be controlled by the normal regulation. 

F15

Jog Speed

Jog speed at low temperatures

Enter the desired jog speed for outside temperatures of -20°C and lower here.

(For outside temperatures b10 and -20, the controller will calculate and 

utilise a speed between the two jog settings.)

F16

LowTempJog

Fan control definition

0: Off

1: The fan is connected to terminal 5-6 and is speed-controlled by an internal phase 

cut. The relay on terminal 15-16 connects at speed requirements of 95% or higher. 

2: The fan is connected to an external speed control device. The speed control signal 

is connected to terminals 28-29. The relay on terminal 15-16 will connect when 

regulation is required. (During external control, the settings F14, F15 and F16 will 

remain in force)

F17

FanCtrlMode

Minimum fan speed

Set the lowest permitted fan speed here. The fan will be stopped if the user enters a 

lower speed.

F18

MinFanSpeed

Maximum fan speed

The fan's top speed can be limited here. The value can be entered by setting the 

nominal speed of 100% to the desired percentage. 

F19

MaxFanSpeed

Manual fan speed control

An override of the fan speed control can be performed here. This function is only 

relevant when the main switch is in service mode.

F20

Manual Fan %

The LED on the controller’s front will show whether Fan is in progress supplied either 

through fan speed control output or fan relay.

Real time clock

When using data communication the clock is automatically adjusted by the system 

unit. If the controller is without data communication, the clock will have a power 

reserve of four hours. 

(Times cannot be set via data com-

munication. Settings are only relevant 

when there is no data communica-

tion).

Switch to day operation

Enter the time at which the control reference becomes the entered set point.

t17

Day start

Change to night operation

Enter the time at which the control reference is raised with r13.

t18

Night start

Clock: Hour setting

t07

Clock: Minute setting

t08

Clock: Date setting

t45

Clock: Month setting

t46

Clock: Year setting

t47

Miscellaneous

Miscellaneous

If the controller is built into a network with data communication, it must have an ad-

dress, and the system unit of the data communication must then know this address.
The address is set between 0 and 240, depending on the system unit and the selected 

data communication. 

o03

The function is not used when the data communication is MODBUS. It is retrieved 

here via the system's scan function.

o04

Access code 1 (Access to all settings)

If the settings in the controller are to be protected with an access code you can set a 

numerical value between 0 and 100. If not, you can cancel the function with setting 0. 

(99 will always give you access).

o05

Acc. code

Controller software version

o08

SW ver

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: