background image

Optyma Plus 

TM 

User 

Guide RS8GD602 © Danfoss 2015-10 

9

Select signal for the display 

Here you define the signal to be shown by the display.

1: Suction pressure in degrees, Ts.

2: Condensing pressure in degrees, Tc.

o17

Display mode

Pressure transmitter settings for Ps 

Working range for pressure transmitter - min. value

o20

MinTransPs

Pressure transmitter settings for Ps

Working range for pressure transmitter - max. value

o21

MaxTransPs

Refrigerant setting 

(only if "r12" = 0)

Before refrigeration is started, the refrigerant must be defined. You may choose be-

tween the following refrigerants

2=R22.  3=R134a. 13=User defined.  17=R507.  19=R404A.  20=R407C. 21=R407A. 

37=R407F.

Warning: Wrong selection of refrigerant may cause damage to the compressor.

Other refrigerants: Here Setting 13 is selected and then three factors -Ref.Fac a1, a2 

and a3 - via AKM must be set.

o30

Refrigerant

Digital input signal - D2

The controller has a digital input 2 which can be used for one of the following func-

tions:

0: The input is not used.

1: Status display from an external safety function (short-circuited =ok for compressor 

operation) 

2: Main switch. Regulation is carried out when the input is short-circuited, and regula-

tion is stopped when the input is put in pos. OFF.

3: Night operation. When the input is short-circuited, there will be regulation for night 

operation.

4: Separate alarm function. Alarm will be given when the input is short-circuited.

5: Separate alarm function. Alarm will be given when the input is opened.

6: Input status, on or off. (DI2 status can be tracked via data communication) 

7: Alarm from the compressor's external speed control.

o37

DI2 config.

Pressure transmitter settings for PC 

Working range for pressure transmitter - min. value

o47

MinTransPc

Pressure transmitter settings for PC

Working range for pressure transmitter - max. value

o48

MaxTransPc

Select the type of condensing unit.

Factory set. 

After the first setting, the value is 'locked' and can only be changed once the control-

ler has been reset to its factory setting. 

When entering the refrigerant setting, the controller will ensure that the 'Unit type' 

and refrigerant are compatible.

o61

Unit type

S3 Configuration

0 = S3 input not used

1 = S3 input used for measuring of discharge temperature

o63

S3 config

Save as factory setting

With this setting you save the controller’s actual settings as a new basic setting (the 

earlier factory settings are overwritten).

o67

-

Define the use of the Taux sensor (S5)

0: Not used

1: Used to measure oil temperature

2: Other use. Measuring of optional temperature.

o69

Taux Config

Period time for heating element in crankcase

Within this period the controller will itself calculate an OFF and ON period.

The time is entered in seconds.

P45

PWM Period

Difference for the heating elements 100% ON point

The difference applies to a number of degrees below the 'Tamb minus Ts = 0 K' value. 

P46

CCH_OnDiff

Difference for the heating elements full OFF point

The difference applies to a number of degrees above the 'Tamb minus Ts = 0 K' value

P47

CCH_OffDiff

Operating time for condensing unit

The condensing unit's operating time can be read out here. The read-out value must 

be multiplied by 1,000 in order to obtain the correct value.

(The displayed value can be adjusted if required)

P48

Unit  Runtime

Operating time for the compressor

The compressors operating time can be read out here. The read-out value must be 

multiplied by 1,000 in order to obtain the correct value.

(The displayed value can be adjusted if required)

P49

Comp Runtime

Operating time for heating element in crankcase

The heating element's operating time can be read out here. The read-out value must 

be multiplied by 1,000 in order to obtain the correct value.

(The displayed value can be adjusted if required)

P50

CCH Runtime

Number of HP alarms

The number of HP alarms can be read out here.

(The displayed value can be adjusted if required)

P51

HP Alarm Cnt

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: