background image

12 

User 

Guide RS8GD602 © Danfoss 2015-10 

Optyma 

Plus 

TM

Settings from 

System manager

Settings from 

AKM (AKM destination)

Log

Alarm relay

Send via

Network

Non

High

Low-High

High

1

X

X

X

X

Middle

2

X

X

X

Low

3

X

X

X

Log only

X

Disabled

Fault message

In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the 

alarm report in the display.

There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation.

A-alarms will not become visible until the set time delay has expired. 

E-alarms, on the other hand, will become visible the moment the error occurs.

(An A alarm will not be visible as long as there is an active E alarm).

Here are the messages that may appear:

Code / Alarm text via data 

communication

Description

Action

A2/---  LP alarm

Low suction pressure

See instructions for the condensing unit

A11/--- No Rfg. sel.

No refrigerant selected

Set o30

A16 /--- DI2 alarm

DI2 alarm

Check the function that sends a signal at the DI2 input

A17 / ---HP Alarm

C73 / DI3 Alarm  (High / low pressure alarm)

See instructions for the condensing unit

A45 /--- Standby mode

Standby position (stopped refrigeration via r12 or DI1-input)

r12 and/or DI1 input will start the regulation

A80 / --- Cond. blocked

Air flow has decreased.

Clean the condensing unit

A96 / --- Max Disc. Temp

Discharge gas temperature is exceeded

See instructions for the condensing unit

A97 / --- Safety alarm

Safety function on DI2 is activated

Check the function that sends a signal at the DI2 input 

and the direction of rotation of the compressor

A98 / --- Drive alarm

Alarm from speed regulation

Check speed regulation

E1 /---  Ctrl. Error

Faults in the controller

Check sensor and connection

E20 /--- Pc Sensor Err

Error on pressure transmitter Pc

E30 /--- Taux Sensor Err

Error on Aux sensor, S5

E31/---Tamb Sensor Err

Error on air sensor, S2

E32 / ---Tdis Sensor Err

Error on discharge sensor, S3

E33 / ---Tsuc Sensor Err

Error on suction gas sensor, S4

E39/--- Ps Sensor Err

Error on pressure transmitter Ps

Data communication

The importance of individual alarms can be defined with a setting. The setting must be carried out in the group "Alarm destinations"

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: