12
User
Guide RS8GD602 © Danfoss 2015-10
Optyma
Plus
TM
Settings from
System manager
Settings from
AKM (AKM destination)
Log
Alarm relay
Send via
Network
Non
High
Low-High
High
1
X
X
X
X
Middle
2
X
X
X
Low
3
X
X
X
Log only
X
Disabled
Fault message
In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the
alarm report in the display.
There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:
Code / Alarm text via data
communication
Description
Action
A2/--- LP alarm
Low suction pressure
See instructions for the condensing unit
A11/--- No Rfg. sel.
No refrigerant selected
Set o30
A16 /--- DI2 alarm
DI2 alarm
Check the function that sends a signal at the DI2 input
A17 / ---HP Alarm
C73 / DI3 Alarm (High / low pressure alarm)
See instructions for the condensing unit
A45 /--- Standby mode
Standby position (stopped refrigeration via r12 or DI1-input)
r12 and/or DI1 input will start the regulation
A80 / --- Cond. blocked
Air flow has decreased.
Clean the condensing unit
A96 / --- Max Disc. Temp
Discharge gas temperature is exceeded
See instructions for the condensing unit
A97 / --- Safety alarm
Safety function on DI2 is activated
Check the function that sends a signal at the DI2 input
and the direction of rotation of the compressor
A98 / --- Drive alarm
Alarm from speed regulation
Check speed regulation
E1 /--- Ctrl. Error
Faults in the controller
Check sensor and connection
E20 /--- Pc Sensor Err
Error on pressure transmitter Pc
E30 /--- Taux Sensor Err
Error on Aux sensor, S5
E31/---Tamb Sensor Err
Error on air sensor, S2
E32 / ---Tdis Sensor Err
Error on discharge sensor, S3
E33 / ---Tsuc Sensor Err
Error on suction gas sensor, S4
E39/--- Ps Sensor Err
Error on pressure transmitter Ps
Data communication
The importance of individual alarms can be defined with a setting. The setting must be carried out in the group "Alarm destinations"