Optyma Plus 

TM 

User 

Guide RS8GD602 © Danfoss 2015-10 

7

Compressor

Compressor control

The start/stop of the controller can be defined in several ways.

Internal only: Here, only the internal main switch in r12 is used.

External: Here, input DI1 is used as a thermostat switch. With this setting, input DI2 

can be defined as an 'external safety' mechanism that can stop the compressor.

Running times

To prevent irregular operation, values can be set for the time the compressor is to run 

once it has been started. And for how long it at least has to be stopped.
Min. ON-time (in seconds)

c01

Min. On time

Min. OFF-time (in seconds)

c02

Min. Off time

Minimum time between cut-in of relay 

(in minutes)

c07

Restart time

Pump down Limit 

Pressure value at which the compressor stops

c33

PumpDownLim

Compressor min. speed

Here the minimum allowable speed for the compressor is set. 

c46

CmpMinSpeed

Compressor start speed

The compressor will not start before the required speed can be achieved

c47

CmpStrSpeed

Compressor max. speed

Upper limit for compressor speed

c48

CmpMaxSpeed

Compressor max. speed during night operation

Upper limit for compressor speed during night operation. During night operation, the 

c48 value is reduced to the percentage value set here

c69

CmpMax % Ngt

Definition of compressor control

0: No external switch for start/stop

1: Input DI1 used to start and stop the compressor

2: The compressor will be speed-controlled with a 0-10 V signal on AO2

c71

Comp mode

Delay time for high discharge  gas temperature 

(in minutes)

When sensor Td records a temperature higher than the limit value entered in r84, the 

timer will start. When the delay time expires, the compressor will be stopped if the 

temperature is still too high. An alarm will also be issued.

c72

Disch. Del

Max. pressure (Max. condensing pressure)

The maximum permitted condensing pressure is set here. If the pressure increases, 

the compressor will be stopped.

c73

PcMax

Difference  for max. pressure (Condensing pressure)

Difference for re-start of compressor if it is cut out due to PcMax.

(All timers must expire before re-start is permitted)

c74

Pc Diff

Minimum suction pressure

Enter the lowest permitted suction pressure here. The compressor is stopped if the 

pressure drops below the minimum value.

c75

PsLP

Suction pressure difference

Difference for re-start of compressor if it is cut out due to PsLP.

(All timers must expire before re-start is permitted)

c76

PsDiff

Amplification factor Kp for compressor regulation

If the Kp value is lowered, the regulation will be slower

c82

Cmp Kp

Integration time Tn for compressor regulation

If the Tn value is increased, regulation will run more smoothly

c83

Comp Tn sec

Liquid Injection Offset

The liquid injection relay is activated when the temperature is over “r84” minus “c88” 

(but only if the compressor is running).

c88

LI Offset

Liquid Injection hysterese

The liquid injection relay is then deactivated when the temperature has dropped to 

“r84” minus “c88” minus “c89”.

c89

LI Hyst

Compressor stop delay after Liquid injection

Compressor ON-time after relay "Aux relay" is went OFF

c90

LI Delay

Desired compressor speed in connection with pressure transmitter faults.

Speed during emergency operation.

c93

CmpEmrgSpeed

Min On time during Low Ambient Temperature and Low Pressure 

c94

c94 LpMinOnTime

Measured Tc for which the Comp min speed is raised to StartSpeed

c95

c95 TcSpeedLim

The LED on the controller’s front will show whether refrigeration is in progress.

Fan

Fan control

Amplification factor Kp

If the KP value is lowered, the fan speed will change.

n04

Kp factor

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: