The compressor is controlled by a signal at the DI1 input. 

The compressor will start once the input is connected. 

Three restrictions have been implemented to avoid frequent start/

stops:

- One for minimum ON time

- One for minimum OFF time

- One for how much time must elapse between two starts.

These three restrictions have the highest priority during 

regulation, and the other functions will wait until they are 

complete before regulation can continue. When the compressor is 

'locked' by a restriction, this can be seen in a status notification.

If the DI3 input is used as a safety stop for the compressor, an 

insufficient input signal will immediately stop the compressor. 

The compressor can be speed-controlled with a voltage signal at 

the AO2 output.

If the compressor has been running for a long period at low speed, 

the speed is increased for a short moment for the purpose of oil-

return.

Maximum discharge gas temperature

The temperature is recorded by sensor Td.

If variable speed control is chosen for the compressor, this control 

will initially reduce the compressor capacity if the Td temperature 

approaches the set maximum value. 

If a higher temperature is detected than the set max. temperature, 

the fan's speed will be set to 100%. If this does not cause the 

temperature to drop, and if the temperature remains high 

after the set delay time, the compressor will be stopped. The 

compressor will only be re-started once the temperature is 

10 K lower than the set value. The above mentioned re-start 

restrictions must also be complete before the compressor can 

start once again.

If the delay time is set to '0', the function will 

not

 stop the 

compressor. The Td sensor can be deactivated (o63).

Liquid injection into economizer port

The controller can activate the liquid injection into economizer 

port if the discharge temperature is approaching the maximum 

allowable temperature.  

Note: Liquid injection function use the Aux Relay.

High pressure monitoring

During regulation, the internal high pressure monitoring function 

is able to detect an over the limit condensing pressure so that the 

regulation can continue.

However, if the C73 setting is exceeded, the compressor will be 

stopped.

If, on the other hand, the signal comes from the interrupted safety 

circuit connected to DI3, the compressor will immediately be 

stopped and the fan will be set to 100%.

When the signal is once again 'OK' at the DI3 input, the regulation 

will resume.

Low pressure monitoring

During regulation, the internal low pressure monitoring function 

will cut out the compressor upon detecting a suction pressure that 

falls below the lower limit, but only once the minimum ON time 

is exceeded. An alarm will be issued. This function will be time 

delayed, if the compressor starts at low ambient temperature.

Pump down limit

The compressor will be stopped if a suction pressure that falls 

below the set value is registered, but only once the minimum ON 

time is exceeded. 

Содержание Optyma Plus

Страница 1: ...Controller for Condensing unit Optyma Plus TM User Guide...

Страница 2: ...value The controller can also control the heating element in the crank case so that oil is kept separate from the refrigerant For excess discharge temperature the liquid injection will be acti vated i...

Страница 3: ...terminal 15 16 will be active when the fan is in operation In menu F17 the user can define which of the two controls to use Jog Min Jog low Jog Speed Speed Required capacity Fan speed at start When th...

Страница 4: ...set delay time the compressor will be stopped The compressor will only be re started once the temperature is 10 K lower than the set value The above mentioned re start restrictions must also be compl...

Страница 5: ...in the master gateway system man ager Heating element in the crankcase The controller has a thermostat function which can control the heating element for the crankcase Oil can thus be kept separate fr...

Страница 6: ...d for the suction pressure Ts in degrees r23 Ts Ref Reference Tc Here the current controller reference for condensing pressure Tc can be read out in degrees r29 Tc Ref Minimum condensing temperature l...

Страница 7: ...the temperature is still too high An alarm will also be issued c72 Disch Del Max pressure Max condensing pressure The maximum permitted condensing pressure is set here If the pressure increases the co...

Страница 8: ...an be limited here The value can be entered by setting the nominal speed of 100 to the desired percentage F19 MaxFanSpeed Manual fan speed control An override of the fan speed control can be performed...

Страница 9: ...type of condensing unit Factory set After the first setting the value is locked and can only be changed once the control ler has been reset to its factory setting When entering the refrigerant settin...

Страница 10: ...e The time the compressor must operate at Boost speed P80 ORM BoostTim Service Service Read pressure Pc u01 Pc bar Read temperature Taux u03 T_aux Status on DI1 input On 1 closed u10 DI1 status Status...

Страница 11: ...us codes have the following meanings Ctrl state Normal regulation S0 0 When the compressor is operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped fo...

Страница 12: ...Set o30 A16 DI2 alarm DI2 alarm Check the function that sends a signal at the DI2 input A17 HP Alarm C73 DI3 Alarm High low pressure alarm See instructions for the condensing unit A45 Standby mode Sta...

Страница 13: ...eady be set to 0 which means stopped regulation 2 Select refrigerant via parameter o30 3 Open parameter r12 and start the regulation Start stop at input DI1 or DI2 must also be activated 4 Go through...

Страница 14: ...ion c83 30 s 360 s 60 s Liquid Injection Offset c88 0 1 K 20 0 K 5 0 K Liquid Injection hysterese c89 10 0 K 30 0 K 15 0 K Compressor stop delay after Liquid injection c90 0 s 10 s 3 s Desired compres...

Страница 15: ...h Read out of compressor operating time Value must be multiplied by 1 000 The value can be adjusted P49 0 h Read out of operating time of heating element in crankcase Value must be multiplied by 1 00...

Страница 16: ...ust then be carried out by one of the other methods Supply voltage 230 V a c This must be the same phase for all 230 V connections FAN Fan connection Speed controlled internally Alarm There is a conne...

Страница 17: ...Min 28 V a c Max 2 0 A Leak 1 mA Relays CE 250 V a c Comp CCH 4 3 A Alarm Fan Aux 4 3 A Analog output 2 pcs 0 10 V d c For external speed control of fans and compressors Min load 10 K ohm Max 1 mA Env...

Страница 18: ...s logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no Optyma PlusTM Condensing unit controller Prepared for data communication Plug for screw terminals not enclos...

Отзывы: