VLT 5000 series
FC 302 series
Parameter 307 Terminal 33, input
5-15 Terminal 33 Digital
Input
7-00 Speed PID Feedback
Source
Options
[0] No function
[0] No operation
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start
anticlockwise, on
[13] Enable start reverse
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference, on
[6] Preset reference, msb [17] Preset reference bit 1
[7] Freeze reference
[19] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed down
[22] Speed down
[10] Choice of Setup,
msb
[24] Setup select bit 1
[11] Choice of Setup,
msb / Speed down
Not supported
[12] Slow down
[29] Slow down
[13] Ramp 2
[34] Ramp bit 0
[14] Mains failure
inverted
Not supported
[24] Pulse feedback
[32] Pulse input,
Parameter 700 = [9]
Frequency input 33
[25] Encoder input 2B
[0] No operation
Parameter 700 = [1] 24 V
encoder
[29] Data change lock
Not supported
Table 5.94 Conversion of Parameter 307
VLT 5000
series
FC 302 series
Parameter 308 Terminal
53, Analogue
Input Voltage
3-15 Reference 1 Source
7-00 Speed PID Feedback Source
1-93 Thermistor Source
4-20 Torque Limit Factor Source
Options
[0] No
Operation
Par. 3-15 Reference resource 1 set to
[0] No function
[1] Reference
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
[2] Feedback
signal
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 7-00 Speed PID Feedback Source
set to [6] Analog input 53
[3] Torque
limit
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 4-20 Torque Limit Factor Source
set to [2] Analog in 53
[4] Thermistor Par. 3-15 Reference resource 1 set to
[0] No function
Par. 1-93 Thermistor Ressource set to
[1] Analog input 53
Table 5.95 Conversion of Parameter 308
VLT 5000 series
FC 302 series
Parameter 309 Terminal 53, min.
scaling
6-10 Terminal 53 Low
Voltage
Range
0 – 10.0 Volt
-10.00 – Par. 6-11
Table 5.96 Conversion of Parameter 309
VLT 5000 series
FC 302 series
Parameter 310 Terminal 53, max.
scaling
6-11 Terminal 53 High
Voltage
Range
0 – 10.0 Volt
Par. 6-10 - 10.00 Volt
Table 5.97 Conversion of Parameter 310
Parameter Mapping Lists
Operating Instructions
24
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
MG37E102
5
5
Содержание MCA 194
Страница 2: ......
Страница 47: ...Index Operating Instructions MG37E102 Danfoss A S Rev 2014 03 06 All rights reserved 45...