VLT 5000 series
FC 302 series
Parameter 319 Terminal 42, Output Digital = Par. 5-32 DO
X30/7 (MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45, Output Digital = Par. 5-33 DO
X30/7 (MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Options
[28] Brake, no brake
warning
Par. 5-32 = [28] Brake, no
brake warning
[29] Brake ready, no
fault
Par. 5-32 = [29] Brake
ready, no fault
[30] Brake fault
Par. 5-32 = [30] Brake fault
(IGBT)
[31] Relay 123
Par. 5-32 = [31] Relay 123
[32] Mechanical brake
control
Par. 5-32 = [32] Mech
brake ctrl
[34] Extended
mechanical brake
control
Par. 5-32 = [32] Mech
brake ctrl
[35] Safety Interlock
Not supported
[36] 0 – 100 Hz
⇒
0 – 20
mA
Not supported
[37] 0 – 100 Hz
⇒
4 – 20
mA
Not supported
[38] 0 – 100 Hz
⇒
0 –
32000 p
Not supported
[39] 0 – f max
⇒
0 – 20
mA
Par. 6-50 = [109] Max Out
freq. 0 – 20 mA
[40] 0 – f max
⇒
4 – 20
mA
Par. 6-50 = [130] Max Out
freq. 4 – 20 mA
[41] 0 – f max
⇒
0 –
32000 p
Par. 5-66 = [109] Max Out
freq. 0 – 32000p Par. 568 =
32000
[42] Ref min – Ref max
⇒
0 – 20 mA
Par. 6-50 = [101] Reference
0 -20 mA
Table 5.108 Conversion of Parameters 319 to 321
VLT 5000 series
FC 302 series
Parameter 319 Terminal 42,
Output
Digital = Par. 5-32 DO X30/7
(MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45,
Output
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Options
[43] Ref min – Ref max
⇒
4 – 20 mA
Par. 6-50 = [131] Reference 4
-20 mA
[44] Ref min – Ref max
⇒
0 - 32000 p
Par. 5-66 = [101] Reference 0
– 32000p Par. 5-68 = 32000
[45] FB min – FB max
⇒
0 – 20 mA
Par. 6-50 = [102] Feedback 0
-20 mA
[46] FB min – FB max
⇒
4 – 20 mA
Par. 6-50 = [132] Feedback 4
-20 mA
[47] FB min – FB max
⇒
0 - 32000 p
Par. 5-66 = [102] Feedback 0
– 32000p Par. 5-68 = 32000
[48] 0 – I max
⇒
0 – 20
mA
Par. 6-50 = [103] Motor
current 0 -20 mA
[49] 0 – I max
⇒
4 – 20
mA
Par. 6-50 = [133] Motor
current 4 -20 mA
[50] 0 – I max
⇒
0 –
32000 p
Par. 5-66 = [103] Motor
current 0 - 32000p Par. 5-68
= 32000
[51] 0 – T lim
⇒
0 – 20
mA
Par. 6-50 = [104] Torque
related to limit 0 - 20 mA
[52] 0 – T lim
⇒
4 – 20
mA
Par. 6-50 = [134] Torque
related to limit 4 - 20 mA
[53] 0 – T lim
⇒
0 –
32000 p
Par. 5-66 = [104] Torque
related to limit 0 – 32000p
Par. 5-68 = 32000
[54] 0 – T nom
⇒
0 –
20 mA
Par. 6-50 = [105] Torque
related to norm 0 - 20 mA
[55] 0 – T nom
⇒
4 –
20 mA
Par. 6-50 = [135] Torque
related to norm 4 - 20 mA
[56] 0 – T nom
⇒
0 –
32000 p
Par. 5-66 = [105] Torque
related to norm 0 – 32000p
Par. 5-68 = 32000
[57] 0 – P nom
⇒
0 –
20 mA
Par. 6-50 = [106] Power
related to norm 0 - 20 mA
[58] 0 – P nom
⇒
4 –
20 mA
Par. 6-50 = [136] Power
related to norm 4 - 20 mA
[59] 0 – P nom
⇒
0 –
32000 p
Par. 5-66 = [106] Power
related to norm 0 – 32000p
Par. 5-68 = 32000
Table 5.109 Conversion of Parameters 319 to 321
Parameter Mapping Lists
Operating Instructions
MG37E102