6 Troubleshooting
6.1 Step-by-step Troubleshooting
1.
Copy the station address from the VLT
®
5000 to
the VLT
®
AutomationDrive.
2.
Cycle power to the FC 302.
3.
The master/PLC now recognises FC 302 as a VLT
®
5000.
4.
The NS LED on the MCA 194 option is now solid
green indicating that communication between
master and slave is established.
If the NS LED flashes, the master/PLC has not recognised
the FC 302 action:
•
Check if station address is the same in the FC 302
as the replaced VLT
®
5000.
•
Check
10-01 Baud Rate Select
. If the frequency
converter has no connection to the master, this
parameter may be set to the wrong baudrate.
•
Check
10-13 Warning Parameter
.
Bit
Warn. Word
[Hex]
Description
0
0001
Bus not active
1
0002
Explicit connection timeout
2
0004
I/O connection
3
0008
Retry limit reached
4
0010
Actual value is not updated
5
0020
CAN bus off
6
0040
I/O send error
7
0080
Initialisation error
8
0100
No bus supply
9
0200
Bus off
10
0400
Error passive
11
0800
Error warning
12
1000
Duplicate MAC ID Error
13
2000
RX queue overrun
14
4000
TX queue overrun
15
8000
CAN overrun
Table 6.1 Warning Word
•
Check
chapter 1.4 Constraints
for more
information on limitations.
Troubleshooting
Operating Instructions
MG37E102
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
43
6
6