VLT 5000 series
FC 302 series
Parameter
311 Terminal 54,
Analogue Input
Voltage
3-16 Reference 2
Source
7-00 Speed PID
Feedback Source
4-20 Torque Limit
Factor Source
1-93 Thermistor
Source
4-21 Speed Limit
Factor Source
Options
[0] No Operation
Par. 3-16 Reference
resource 2 set to [0]
No function
[1] Reference
Par. 3-16 Reference
resource 1 set to [2]
Analog input 53
[2] Torque limit
Par. 4-20 Torque
Limit Factor Source
set to [6] Analog in
54
[3] Thermistor
Par. 1-93 Thermistor
Ressource set to [2]
Analog input 54
[4] Relative
reference
Not supported
[5] Max. torque
frequency
Par. 4-21 Speed
Limit Factor Source
set to [6] Analog in
54
Table 5.98 Conversion of Parameter 311
VLT 5000 series
FC 302 series
Parameter 312 Terminal 54, min.
scaling
6-20 Terminal 54 Low
Voltage
Range
0 – 10.0 Volt
-10.00 – Par. 6-21
Table 5.99 Conversion of Parameter 312
VLT 5000 series
FC 302 series
Parameter 313 Terminal 54, max.
scaling
6-21 Terminal 54 High
Voltage
Range
0 – 10.0 Volt
Par. 6-20 - 10.00 Volt
Table 5.100 Conversion of Parameter 313
VLT 5000 series FC 302 series
Parameter 314 Terminal 60,
Analogue Input
current
3-17 Reference 3 Source
7-00 Speed PID Feedback Source
1-93 Thermistor Source
4-20 Torque Limit Factor Source
Options
[0] No
Operation
Par. 3-17 Reference resource 3 set
to [0] No function
[1] Reference
Par. 3-17 Reference resource 3 set
to [2] Analog input 54 Par. 7-00
Speed PID
Feedback Source set to [7] Analog
input 54
[2] Feedback
signal
Par. 7-00 Speed PID Feedback
Source set to [7] Analog input 54
[3] Torque limit Par. 3-17 Reference resource 3 set
to [2] Analog input 54 Par. 4-20
Torque Limit
Factor Source set to [6] Analog in
54
[4] Relative
reference
Not supported
Comments The HW switch S202 for analogue input 54 must be
set to current (ON).
Table 5.101 Conversion of Parameter 314
VLT 5000 series
FC 302 series
Parameter 315 Terminal 60, min.
scaling
6-22 Terminal 54 Low
Current
Range
0.0 – 20.0 mA
0.00 – Par. 6-23
Table 5.102 Conversion of Parameter 315
VLT 5000 series
FC 302 series
Parameter 316 Terminal 60, max.
scaling
6-23 Teminal 54 High
Current
Range
0.0 – 20.0 mA
Par. 6-22 - 20.00 mA
Table 5.103 Conversion of Parameter 316
VLT 5000 series
FC 302 series
Parameter
317 Time Out
6-00 Live Zero Timeout Time
Range
0 – 99 sec
0 – 99 sec
Table 5.104 Conversion of Parameter 317
Parameter Mapping Lists
Operating Instructions
MG37E102
Danfoss A/S © Rev. 2014-03-06 All rights reserved.