4.1.3 Start-up
After setting the station address from VLT
®
5000 to VLT
®
AutomationDrive, cycle power on the frequency converter
to activate the new address. The master/PLC now
recognises the frequency converter as VLT
®
5000. A solid
green NS LED on the MCA 194 option indicates that
communication between the master and the frequency
converter is established. If the NS LED flashes, the
master/PLC has not recognised the frequency converter.
For more information, refer to
chapter 6.1 Step-by-step
Troubleshooting
.
4.2 LED Behaviour
The option has 2 bi-coloured LEDs, as shown in
Table 4.2
. The status of the LEDs is shown in
Table 4.3
and
Table 4.4
.
LED label
Description
NS
Network Status
MS
Module Status ( DP-V1 communication)
Table 4.2 Bi Coloured LEDs
State
Bi-colour LED
Status
No Power
Off
There is no power applied to the option
Device
operational
Green
The DeviceNet option is operating in
normal condition.
Standby
Green
The DeviceNet option needs commis-
sioning due to configuration missing,
incomplete or incorrect.
Minor fault
Red
Recoverable fault.
Unrecoverable
fault
Red
Unrecoverable fault, may need
replacing.
Self test
Green
The DeviceNet option is in Self-test
mode.
Red
Table 4.3 LED: Module Status (MS)
State
Bi-colour LED
Status
No Power/Not on-
line
Off
The option has not completed
“Duplicate MAC ID” test yet or may not
be powered.
On-line, not
connected
Green
The option is on-line, but not allocated
to a master.
On-line and
connected
Green
The DeviceNet option is on-line and
connected to a master.
Connection time-
out
Red
One or more I/O connections are in
time-out state.
Critical link failure Red
Table 4.4 LED: Network Status (NS)
NOTICE
The LED status patterns of the MCA 194 are not compatible with the patterns of the VLT
®
5000 DeviceNet LEDs.
Commissioning
Operating Instructions
12
Danfoss A/S © Rev. 2014-03-06 All rights reserved.