4 Commissioning
4.1 Configure the DeviceNet Network
All DeviceNet stations connected to the same bus network
must have a unique station address.
Before a VLT
®
5000 can be replaced with an FC 302 with
MCA 194, only the station address and baud rate needs to
be configured in the FC 302.
The DeviceNet address of the FC 302 can be selected via:
•
Hardware switches
•
Parameter
10-02 MAC ID
(default 63)
•
Class code 0X03, Instance 1, Attribute 1
NOTICE
After installing DeviceNet Converter MCA 194, check that
8-02 Control Source
is set to
[3] Option A
.
4.1.1 Setting the DeviceNet Address using
the Hardware Switches
Read the hardware switches during power-up. When
switches are changed, perform a power down-up
immediately to activate the changes.
NOTICE
The address change comes into effect at the next power-
up, and can be read in
10-02 MAC ID
.
Using the hardware switches, select an address range from
0 to 63 (factory setting 63) according to
Illustration 4.1
: ON
= 1, OFF = 0
130BD825.10
MCA 194
DeviceNet
Converter
MS
NS
Option A
130B5601
NS
MS
ON
OFF
S600
ON
OFF
ON
S300
ON
ON
1
2
3
4
5
6
7
8
Illustration 4.1 DeviceNet Converter Option A
VLT
®
5000
FC 302
Switch
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
Address
+32
+16
+8
+4
+2
+1
-
-
-
-
+32
+16
+8
+4
+2
+1
Example:
1
0
0
0
0
0
1
-
-
-
-
0
0
0
0
0
1
35
1
0
0
0
1
1
-
-
-
-
1
0
0
0
1
1
52
1
1
0
1
0
0
-
-
-
-
1
1
0
1
0
0
Table 4.1 Hardware Switches
4.1.2 Setting the DeviceNet Address via
10-02 MAC ID
Setting the address via parameter
10-02 MAC ID
or the
DeviceNet Class code 0X03, Instance 1, Attribute 1, is
possible, if the hardware switches are all set in the "On"
position. The new address becomes active at the next
power-up.
Commissioning
Operating Instructions
MG37E102
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
11