FCM 300 Series
43
MG.03.B6.02 - VLT is a registered Danfoss trademark
015 Local jog (LOCAL JOGGING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the jog function can be enabled/
disabled on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the [JOG]
key will be inactive.
016 Local reversing
(LOCAL REVERSING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reversing function can be
enabled/disabled on the control panel.
This key can only be used if parameter 002 has
been set to
Local operation
[1] and parameter 013
to
LCP control with open loop
[1] or
LCP control as
parameter 100
[3].
Description of choice:
If
Disable
[0] is selected in this parameter, the [FWD/
REV] key will be inactive.
See parameter 200.
017 Local reset of trip (LOCAL RESET)
Value:
Not possible (DISABLE)
[0]
✭
Possible (ENABLE)
[1]
Function:
In this parameter, the reset function can be
selected/removed from the keyboard.
This key can be used when parameter 002 has
been set for
Remote control
[0] or
Local control
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the
[RESET] key will be inactive.
NB!
NB!
NB!
NB!
NB!
Only select
Disable
[0] if an external reset
signal has been connected via the digital
inputs.
✭
=
factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
018 Lock for data change
(DATA CHANGE LOCK)
Value:
✭
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
In this parameter, the software can "lock" the
control, which means that data changes cannot be
made via LCP 2 (however, this is still possible via the
serial communication port).
Description of choice:
If
Locked
[1] is selected, data changes cannot be
made.
Operation & Display
019 Operating state at power up, local
control (POWER UP ACTION)
Value:
Auto restart, use saved ref.(AUTO RESTART)
[0]
✭
Forced stop, use saved ref. (LOCAL=STOP)
[1]
Forced stop, set ref. to 0
(LOCAL=STOP, REF=0)
[2]
Function:
Setting of the desired operating mode when the
mains voltage is reconnected.
This function can only be active in connection with
Local control
[1] in parameter 002.
Description of choice:
Auto restart, use saved ref.
[0] is selected if the unit
is to start up with the same local reference (set in
parameter 003) and the same start/stop conditions
(given via the [START/STOP] keys) that the FC motor
had before it was switched off.
Forced stop, use saved ref.
[1] is used if the unit is to
remain stopped when the mains voltage is
connected, until the [START] key is pressed. After the
start command, the local reference used is set in
parameter 003.
Forced stop, set ref. to 0
[2] is selected if the unit is
to remain stopped when the mains voltage is
connected. Local reference (parameter 003) is reset.
NB!
In remote controlled operation (parameter
002), the start/stop condition at power up will
depend on the external control signals. If
Latched start
is selected in parameter 332-335, the
motor will remain stopped at power up.