List of warnings and alarms
The table gives the different warnings and alarms and
indicates whether the fault locks the FC motor. After
Trip locked, the mains supply must be cut and the
fault must be corrected. Reconnect the mains supply
and reset the FC motor before being ready.
No.
Description
Warning
Trip Alarm
Trip locked
2
Live zero fault (LIVE ZERO ERROR)
X
X
4
Phase loss (MAINS PHASE LOSS)
X
X
X
5
Voltage warning high (DC LINK VOLTAGE HIGH)
X
6
Voltage warning low (DC LINK VOLTAGE LOW)
X
7
Overvoltage (DC LINK OVERVOLT)
X
X
8
Undervoltage (DC LINK UNDERVOLT)
X
9
Inverter overload (INVERTER TIME)
X
X
11
Motor thermistor (MOTOR THERMISTOR)
X
12
Current limit (CURRENT LIMIT)
X
13
Overcurrent (OVERCURRENT)
X
X
14
Earth fault (EARTH FAULT)
X
X
15
Supply fault (SWITCH MODE FAULT)
X
X
16
Short-circuit (CURR.SHORT CIRCUIT)
X
X
17
Standard bus timeout (STD BUS TIMEOUT)
X
X
18
HPFB bus timeout (HPFB TIMEOUT)
X
X
33
Out of frequency range (OUT FREQ RNG/ROT LIM)
X
34
HPFB error (HPFB ALARM)
X
X
35
Inrush fault (INRUSH FAULT)
X
X
36
Overtemperature (OVERTEMPERATURE)
X
X
37
Internal error (INTERNAL ERROR)
X
X
■
■
■
■
■
Wherever a cross is placed under both Warning and
Alarm, this can mean that a warning precedes the
alarm. It can also mean that it is possible to program
whether a given fault is to result in a warning or an
alarm. After a trip, alarm and warning will flash, but if
the fault is removed, only alarm will flash. After a
reset, the FC motor will be ready to start operation
again.
W
a
rn
ings and alarms
What if the motor does not start?
-
Make sure no parameters have been changed
from initial delivery status (factory setting). Use
the Local Control Panel or serial port to reset to
factory setting.
-
Make sure no STOP command have been
issued by the optional control panel keyboard
(local stop) Control Panel STOP can only be
restarted by the Control Panel START button.
■
■
■
■
■
Warning:
Extreme care must be taken when
operating the unit with open lid.
-
Check the Light Emitting Diodes visible through a
hole in the inside isolation cover (see drawing
on page 16), follow table below.
Green
Green
Green
Green
Green
Y
Y
Y
Y
Yellow
ellow
ellow
ellow
ellow
Red
Red
Red
Red
Red
Action
Action
Action
Action
Action
LED 302
LED 302
LED 302
LED 302
LED 302
LED 301
LED 301
LED 301
LED 301
LED 301
LED 300
LED 300
LED 300
LED 300
LED 300
OFF
OFF
OFF
Apply power
ON
OFF
OFF
Apply start and reference
start and reference
start and reference
start and reference
start and reference signals , (see drawing on page 16)
ON
OFF
ON
Apply and remove reset
reset
reset
reset
reset signal according to the drawing on page 16.
ON
ON
ON
Switch off power until all LED's have turned off
For further information see the quick setup MG.03.Fx.xx.