FCM 300 Series
MG.03.B6.02 - VLT is a registered Danfoss trademark
36
Function/settings
Function/settings
Function/settings
Function/settings
Function/settings
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Start)
Key (Stop)
Key (Stop)
Key (Stop)
Key (Stop)
Key (Stop)
Default - Dual speed operation
Default - Dual speed operation
Default - Dual speed operation
Default - Dual speed operation
Default - Dual speed operation
Run on set
Run on
Stop (and
(connect purple wire):
(connect purple wire):
(connect purple wire):
(connect purple wire):
(connect purple wire):
reference
10 Hz**
reset* - if trip)
No changes to factory setting.
(+/-)
jog speed
Function 2 - Dual mode operation
Function 2 - Dual mode operation
Function 2 - Dual mode operation
Function 2 - Dual mode operation
Function 2 - Dual mode operation
(connect purple wire):
(connect purple wire):
(connect purple wire):
(connect purple wire):
(connect purple wire):
Run with
Run with
Stop (and
Select desired modes of operation
Setup 1
Setup 2
reset* - if trip)
in Setups 1 and 2 (use para. 4-6)
Parameter 335 = 18 (select Setup)
Function 3 - Dual direction operation
Function 3 - Dual direction operation
Function 3 - Dual direction operation
Function 3 - Dual direction operation
Function 3 - Dual direction operation
(connect grey wire):
(connect grey wire):
(connect grey wire):
(connect grey wire):
(connect grey wire):
Run
Run
Stop (and
Parameter 335 = 10 (start reversing)
forward
reverse
reset* - if trip)
Parameter 200 = 1 (both directions)
*If no reset is required,
do not connect the brown wire
**or set parameter 213
At power up the unit will always be in stop mode.
Set reference will be stored during power down. If
permanent start mode is desired, connect terminal
6 to terminal 4 and do not connect purple/grey
wire to terminal 4. This means the stop function on
LOP is disabled.
NB!
NB!
NB!
NB!
NB!
After fitting, cut off or isolate excess wire.
Local Control
Use the +/- keys to set reference
Colour of wire
Colour of wire
Colour of wire
Colour of wire
Colour of wire
T
T
T
T
Terminal
erminal
erminal
erminal
erminal
Function
Function
Function
Function
Function
White
2
Reference
Brown
3
Reset
Purple or Grey
4
See table under button
Green
5
See table under button
Red
6
+24V
Yellow
7
+10V
Blue
8
Ground
W
W
W
W
W iring
iring
iring
iring
iring
■
Local Operation Pad (LOP)
■
Remote mounting kit cont.
Panel
door
Control unit