FCM 300 Series
MG.03.B6.02 - VLT is a registered Danfoss trademark
16
Terminal arrangement (for installation see quick setup, MG.03.Fx.xx)
T
echnical data
Screen
Externals:
- Enclosure ............................................................................................................................. IP 55 (IP56, IP66)
- Vibration test ........................................................................................................... (IEC 68 see page 85) 1 g
- Max. relative humidity ................................................... 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
- Ambient temperature ....................................................................... Max. 40°C (24-hour average max. 35°C)
Derating for high ambient temperature, see chapter 10.
- Min. ambient temperature in full operation ................................................................................................. 0°C
- Min. ambient temperature at reduced performance .............................................................................. -10°C
- Temperature during storage/transport ..................................................................................... -25 - +65/70°C
- Max. altitude above sea level .............................................................................................................. 1000 m
Derating for air pressure, see chapter 10.
- EMC standards applied, Emission ................................... EN 50081-1/2, EN 61800-3, EN 55011, EN 55014
Immunity ................... EN 50082-2, EN 61000-4-2, IEC 1000-4-3, EN 61000-4-4
EN 61000-4-5, ENV 50140, ENV 50141
- Safety standards applied, ............................................................................ EN 60146, EN 50178, EN 60204
UL508
Protection:
•
•
•
•
•
Thermal overload protection of motor and electronics.
•
•
•
•
•
Monitoring of the intermediate circuit voltage ensures that the inverter cuts out if the intermediate circuit
voltage gets too high or too low.
•
•
•
•
•
If a mains phase is missing, the inverter will cut out when a load is placed on the motor.