67
MG.03.B6.02 - VLT is a registered Danfoss trademark
✭
=
factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
Serial communication
525 Data read-out: DC link voltage
(DC LINK VOLTAGE)
Value:
XXXX V
[XXXX]
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
The value shown is a measured value.
The value is filtered, which means that approx. 1.3
seconds may pass from an input value changes until
the data read-out changes values.
This value is updated every 320 ms.
527 Data read-out:
F
FC therm.
(FC THERMAL)
Value:
0 - 100%
[0 - 100]
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
Only whole numbers are displayed.
This value is updated every 160 ms.
528 Data read-out: Digital input
(DIGITAL INPUT)
Value:
Unit
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
The value shown indicates the signal status from the
4 digital terminals (2, 3, 4, and 5).
This value is updated every 20 ms.
533 Data read-out: External reference %
(EXT. REFERENCE)
Value:
-200.0 - +200.0 %
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
The value stated gives, as a percentage, the sum of
external references (sum of analogue/bus/pulse).
This value is updated every 80 ms.
534 Data read-out: Status word, binary
(STATUS WORD [HEX])
Value:
Unit
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
Indicates the status word transmitted via the serial
communication port.