FCM 300 Series
39
MG.03.B6.02 - VLT is a registered Danfoss trademark
Description of choice:
The Factory Setup
[0] contains the factory data and
can be used as a data source if the other Setups
are to be returned to a known state.
Setups
1
[1] and 2 [2] are individual Setups which can
be used as required. They can be programmed freely,
regardless of the Setup selected as the Active Setup
and thus controlling the functions of the FC motor.
NB!
If a general change of data or a copying to the
Active Setup is effected, this immediately
affects the functioning of the unit.
006 Copying of Setups (SETUP COPY)
Settings:
✭
No copying (NO COPY)
[0]
Copy to Setup 1 from # (COPY TO SETUP 1)
[1]
Copy to Setup 2 from # (COPY TO SETUP 2)
[2]
Copy to Setup all from # (COPY TO ALL)
[5]
# = the Setup selected in parameter 005
Function:
A copy is made from the Setup selected in parameter
005 to one of the other Setups or to all the other
Setups simultaneously.
NB!
Copying is only possible in Stop Mode (motor
stopped on a Stop command).
Copying will take max. 3 seconds and has ended
when parameter 006 has returned to value 0.
004 Active Setup (ACTIVE SETUP)
Settings:
Factory Setup (FACTORY SETUP)
[0]
✭
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Multi Setup (MULTI SETUP)
[5]
Function:
The choice in this parameter defines the Setup
number you want to control the functions of the FC
motor.
All parameters can be programmed in two individual
parameter Setups, Setup 1 and Setup 2. In addition,
there is a pre-programmed Setup, called Factory
Setup, that cannot be modified.
Description of choice:
Factory Setup
[0] contains the factory data. Can be
used as a data source if the other Setups are to be
returned to a known state.
Parameters 005 and 006 allow copying from one
Setup to the other.
Setups
1 [1] and 2 [2] are two individual Setups that
can be selected as required.
Multi-Setup
[5] is used if remote-mounting switching
between Setups is desired. Terminals 2, 3, 4, and 5
as well as the serial communication port can be used
for switching between Setups.
005 Programming Setup (EDIT SETUP)
Settings:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
✭
Active Setup (ACTIVE SETUP)
[5]
Function:
The choice is of the Setup in which programming
(change of data) is to occur during operation. It is
possible to programme the two Setups independently
of the Setup selected as the Active Setup (selected in
parameter 004).
✭
=
factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
Operation & Display