FCM 300 Series
MG.03.B6.02 - VLT is a registered Danfoss trademark
56
✭
=
factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
339 Terminal 2, max. scaling
(AI 2 SCALE HIGH)
Settings:
0.0 - 10.0 V
[0 - 100]
★
10.0 V
[100]
Function:
This parameter is used for setting the signal value that
corresponds to the maximum reference value set in
parameter 205.
Description of choice:
Set the desired voltage value.
340 Terminal 9, output functions (OUTPUT FUNC.)
Settings:
✭
No function
(NO OPERATION)
[0]
Ready signal
(UNIT READY)
[1]
Enable, no warning
(ENABLE/NO WARNING)
[2]
Running
(MOTOR RUNNING)
[3]
Running, no warning
(RUNNING NO WARNING)
[4]
Running on reference, no warning
(RUNNING ON REFERENCE)
[5]
Fault
(FAULT)
[6]
Fault or warning
(FAULT OR WARNING)
[7]
Current limit
(CURRENT LIMIT)
[8]
Thermal warning
(THERMAL WARNING)
[9]
Reversing
(REVERSE)
[10]
Off 123
(OFF 123 RELAY)
[11]
Actual frequency 0-20 mA
(0-FMAX = 0-20 mA)
[12]
Actual frequency 4-20 mA
(0-FMAX = 4-20 mA)
[13]
Reference
MIN
- reference
MAX
: 0-20 mA
(REF MIN-MAX =0-20 mA)
[14]
Reference
MIN
- reference
MAX
: 4-20 mA
(REF MIN-MAX =4-20 mA)
[15]
Feedback
MIN
- feedback
MAX
: 0-20 mA
(FB MIN-MAX =0-20 mA)
[16]
Feedback
MIN
- feedback
MAX
: 4-20 mA
(FB MIN-MAX =4-20 mA)
[17]
Actual current 0-20 mA
(0-IMAX = 0-20 mA)
[18]
Actual current 4-20 mA
(0-IMAX = 4-20 mA)
[19]
Mechanical brake
(MECHANICAL BRAKE)
[20]
Function:
This output can act both as a digital and an
analogue output. If used as a digital output (data
value [0]-[20]), a 24 V DC signal is transmitted; if
used as an analogue output either a 0-20 mA
signal, or a 4-20 mA signal output.
Description of choice:
Unit Ready signal
, the FC motor is ready for use.
Enable/no warning
, the FC motor is ready for use; no
start or stop command has been given (start/disable).
No warning.
Motor Running
, the output frequency is higher than
0.1 Hz. A start command has been given.
Running no warning
, the output frequency is higher
than 0.1 Hz. A start command has been given. No
warning.
Running on reference, no warning
, speed according
to reference. No warning.
Fault
, output is activated by alarm.
Fault or warning
, the output is activated by alarm or
warning.
Current limit,
the current limit in parameter 221 has
been exceeded.
Thermal warning,
above the temperature limit in the
frequency converter.
Reverse
. Logic '1' = relay activated, 24 V DC on the
output when the direction of rotation of the motor is
clockwise. Logic '0' = relay not activated, no signal
on the output, when the direction of rotation of the
motor is counter-clockwise.
Inputs and outputs