FC 300 CANopen
- P a r a m e t e r s -
46
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
-
Output frequency = JOG freq.:
The motor runs at
JOG frequency until communication resumes.
-
Output frequency = Max. freq..
The motor runs at
maximum frequency until communication
resumes.
-
Stop with trip:
The motor stops. You need to reset
the frequency converter, see explanation above.
Select set-up x:
This type of time-out function is used for
changing set-up on a control word time-out. If
communication resumes causing the time-out
situation to disappear, par. 8-05
End-of-time-out
Function
defines whether to resume the set-up
used before the time-out or to hold the set-up
endorsed by the time-out function.
Note that the following parameters have to be
configured for the set-up change to occur on a
time-out. Par. 0-10
Active set-up
has to be set to
Multi set-up
along with the relevant linking set in
par. 0-12
This Set-up Linked To
.
8-05 End-of-timeout Function
Option:
*Hold
set-up
[0]
Resume
set-up
[1]
Function:
Defines the action after receiving a valid control
word upon a time-out. This only applies if set-up
1-4 has been selected in par. 8-04.
Hold:
The drive holds the set-up selected in par. 8-
04 and displays a warning, until par. 8-06
toggles. Then the drive resumes its original set-
up.
Resume:
The drive resumes the original set-up.
8-06 Reset Control Word Timeout
Option:
*Do not reset
[0]
Do
reset
[1]
Function:
Used for returning the drive to the original set-up
after a Control word timeout.
After setting the value to “Do Reset”[1], it returns
to “Do not reset”[0].
8-07 DiagnosisTrigger
Option:
*Disable
[0]
Trigger on alarms
[1]
Trigger
alarms/warn.
[2]
Function:
This parameter has no function for CANopen.
8-10 Control Word Profile
Option:
*FC
profile
[0]
CANopen DSP 402
[5]
Function:
Selects the interpretation of the control and
status words. The installed option in slot A
determines the valid selection.
8-50 Coasting Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Allows a choice between controlling the coasting
function via the terminals (digital input) and/ or
via the bus.
NB!
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital and
control word.
8-51 Quick Stop Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Allows a choice between controlling the Quick
Stop function via the terminals (digital input)
and/or via the bus.
NB!
This parameter is active only when
parameter 8-01
Control site
is set to [0]
Digital and control word.
8-52 DC brake select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Allows a choice between controlling the DC brake
via the terminals (digital input) and/or via the
bus.
NB!
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital and
control word.
8-53 Start Select