FC 300 CANopen
14
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
How to Configure the System
Set the CANopen Address
All CANopen stations that are connected to the same bus network must have a unique station address. The
CANopen address of a FC 300 can be selected via:
-
Parameter 10-02
Drive Node ID
(default 127)
NB!:
Switch off the power supply before changing the hardware switches.
Set the CANopen Address via Parameter 10-02
Drive Node ID
:
The address can be set via parameter 10-02
Drive Node ID.
The hardware switches has no functionality.
The address change will come into effect at the next power-up.
Set the CANopen Baud Rate
All CANopen stations connected to the same bus network must have the same Baud rate. The baud rate of
an FC 300 can be selected via:
-
Parameter 10-01
Baudrate Select
(default 125 kbps)
Set the CANopen Baud Rate via Parameter 10-01
Baudrate select
:
The baud rate can be set via parameter 10-01
Baudrate select.
Hardware switches have no functionality
(disabled)