FC 300 CANopen
- H o w t o C o n t r o l t h e F C 3 0 0 -
24
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
DSP 402 Control Profile
Control Word according to DSP 402
profile.
(Par. 8-10 = DSP 402 profile)
Master
→
slave
CTW Speed
ref.
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Explanation of the Bits:
Bit 00, Switch OFF/ON:
Bit 00= "0" execute transition 2, 6 or 8.
Bit 00 = "1" execute transition 3.
Bit 01, Disable/Enable Voltage:
Bit 01= "0" execute transition 9, 10 or 12.
Bit 01 = "1" = “Enable Voltage“.
Bit 02, Quick stop/Run:
Bit 02= "0" execute transition 7, 10 or 11.
Bit 02 = "1" = Quick stop not active.
Bit 03, Disable/enable Operation:
Bit 03= "0" execute transition 5.
Bit 03 = "1" = “Enable operation“.
Bit 04, Quick-stop/ramp:
Bit 04= "0" execute transition 7 or 11, Quick
stop.
Bit 04 = "1" = Enable ramp.
Bit 05, Freeze output frequency/run enable:
Bit 05 = "0" means that the given output
frequency is maintained even if the reference is
changed.
Bit 05 = "1" means that the frequency
converter is again able to regulate, and the
given reference is followed.
Bit 06, Ramp stop/start:
Bit06= "0" The VLT controls the motor down to
stop.
Bit 01 = "1" = Start command to the VLT is
given.
Bit 07, No function/reset:
Reset of trip.
Bit 07 = "0" means that there is no reset.
Bit 07 = "1" means that a trip is reset.
Bit 08, 09 and 10:
DSP402 reserved.
Bit 11, Jog 1 OFF/ON:
Activation of pre-programmed speed in
parameter 8-90 (Bus JOG 1).
JOG 1 is only possible if Bit 04 = "0", and bit
00 to 03 = "1".
Bit 12:
Danfoss reserved.
Bits 13/14, Selection of Setup:
Bits 13 and 14 are used for choosing among
the four menu Setups in accordance with the
following table:
Bit
14
Bit
13
Setup
0 0
1
0 1
2
1 0
3
1 1
4
Bit 15, Forward/reversing:
Bit 15 = "0" leads to no reversing.
Bit 15 = "1" leads to reversing.
Note: In factory setting reversing is set to
[digital] in par. 8-54
Reversing select
.
Bit
Bit value = 0
Bit value = 1
00
Switch off
Switch on
01
Disable voltage
Enable voltage
02 Quick
stop
run
03
Disable operation
Enable operation
04
Disable ramp
Enable ramp
05 Freeze
Run
enable
06 Ramp
stop
Start
07 No
function
Reset
08 Reserved
09 Reserved
10 Reserved
11
Jog 1 OFF
Jog1 ON
12 Reserved
13
Setup select (LSB)
14
Setup select (MSB)
15 Forward
Reversing