![Danfoss FC 300 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/danfoss/fc-300/fc-300_manual_3469954036.webp)
FC 300 CANopen
36
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
Transmit PDO
The transmission type is set to 255. Each new event initiates new transmit data. The inhibit time
defines a delay time, after which the data will be transmitted.
The following overview shows the transmit (write) PDOs:
PDO
No.
Index Link
to
PDO
(COB-ID)
Mapping
Object
Index
Mapping Object Name
Comment
1
1800h
1
(180h)
6041h
Status word
shows status
6
1805h
2
(280h)
6041h
6044h
Status word
vl_control_effort (RPM)
shows the status and
actual speed (vl)
21 1814h 3
(380h)
6041h
6044h
2f10h/0
2f10h/1
Status word
vl_control_effort (RPM)
process data word 1
(1051[0])
process data word 2
(1051[1])
22 1815h 4
(480h) 2f10h/2
2f10h/3
2f10h/4
2f10h/5
process data word 3
(1051[2])
process data word 4
(1051[3]) process data
word 5 (1051[4])
process data word 6
(1051[5])
1
st
transmit PDO
Index
Subindex Comment
Default Value
1800 h
0
number of entries
3
1
COB-ID used by PDO
180h + node-ID
2
transmission type
255 (change of state)
3
inhibit time
0
4
not used
-
1A00 h 0
number of mapped objects
1
1
Status word
60410010 h
6
th
transmit PDO
Index
Subindex Comment
Default Value
1805 h
0
number of entries
3
1
COB-ID used by PDO
280h + node -ID
2
transmission type
255
3
inhibit time
0
4
not used
-
1A05 h 0
number of mapped objects
2
1
statusword
60400010 h
2
vl_control_effort (RPM)
60440010 h