Status Word according to DSP 402 profile.
(Par. 8-10 = DSP 402 profile)
Slave
→
master
STW Output
freq.
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Explanation of the Bits:
Bit 00, Not ready to switch on/Ready to
switch on:
Bit 00 = "0" state less than “Ready to switch
on”.
Bit 00 = "1" state at least = “Ready to
Switch on”.
Bit 01, Switch off/Switch on:
Bit 00 = "0" state less than “Switched on”.
Bit 00 = "1" state at least = “Switched on”.
Bit 02, Operation disable/Operation enable:
Bit 00 = "0" state less than “Operation
enable”.
Bit 00 = "1" state at least = “Operation
enable”.
Bit 03, No fault/trip:
Bit 03 = "0" means that the drive is not in a
fault condition.
Bit 03 = "1" means that the drive has
tripped and needs a reset signal in order
to run.
Bit 04, Voltage disable/Voltage enable:
Bit 04 = "0" means that control word bit 01 =
"1".
Bit 04 = "1" means that control word bit 01 =
"0".
Bit 05, Quick stop/Run:
Bit 05 = "0" means that control word bit 02 =
"1".
Bit 05 = "1" means that control word bit 02 =
"0".
Bit 06, Start enable/Start disable:
Bit 06 = "0" state is not “Switch on disable”.
Bit 06 = "1" state = “Switch on enable”.
Bit 07, No warning/Warning:
Bit 07 = "0" means that there is no warning.
situation.
Bit 07 = "1" means that a warning has
occurred.
Bit 08, Danfoss reserved:
Bit 09, Remote disable/Remote enable:
Bit 09 = "0" means that the drive has been
stopped by means of the stop key on the LCP,
or that [Local] has been selected in parameter
3-13
Reference site
.
Bit 09 = "1" means that it is possible to control
the drive converter via the serial port.
Bit 10, Set point not reached/Set point
reached:
Bit 10 = "0" means that the actual motor
speed is different from the speed reference set.
This can be the case while the speed is ramped
up/down during start/stop.
Bit 10 = "1" means that the present motor
speed equals the speed reference set.
Bit 11, Speed limit not active/speed limit
active:
Bit 11 = "0" means that the output frequency
is out of the range set in par. 4-11/4-12
Motor
Speed low Limit RPM/Hz
or par. 4-13/4-14
Motor Speed high Limit RPM/Hz
.
Bit 11 = "1" means that the output frequency
is within the mentioned range.
Bit
Bit value = 0
Bit value = 1
00
Not ready to
switch ON
Ready to switch ON
01
Switched OFF
Switched ON
02 Operation disabled
Operation enabled
03 No
malfunction
Malfunction
04
Voltage disabled
Voltage enabled
05 Quick
stop
Run
06
Switch on disable
Switch on enable
07 No
warning
Warning
08 Reserved
09
Remote disabled
Remote enabled
10
Set point not
reached
Set point reached
11
Speed limit not
active
Speed limit active
12 Reserved
13 Reserved
14 Not
running
Running
15 Reserved