FC 300 CANopen
- H o w t o C o n t r o l t h e F C 3 0 0 -
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
23
Index, sub-index Meaning
1010h 0
Largest sub-index supported
1010h 1
Save option parameters
1010h 4
Save all parameters, including option parameters (Edit Set-up)
1010h 5
Save all parameters, including option parameters (all set-ups)
Writing the value “save” (0x65766c173) to sub-index 5 will save all drive
parameters of all set-ups
into non-volatile memory, all other values must be rejected. Sub-index 4 will do the same for the Edit
Set-up. This is handled via par. 10-31
Store data values
.
1011h Restore default parameters
Use this object to set the drive to factory default, by writing the value “load to sub-index 1. The
parameters will be set to default after the next power cycle, which has to be initiated manually.
Index, sub-index Meaning
1011h 0
Largest sub-index supported
1011h 1
Restore all default parameters
1014h COB ID emergency object
This object defines the COB-ID under which the emergency object (EMCY) is sent.
Index, sub-index Meaning
1014h 0
COB ID
1018h Identity object
This object contains general information about the device.
The Vendor ID (sub-index 1h) contains a unique value allocated to each manufacturer.
The manufacturer-specific Product code (sub-index 2h) identifies a specific device version.
The manufacturer-specific Revision number (sub-index 3h) consists of a major revision number and a
minor revision number. The major revision number identifies a specific CANopen behavior. If the
CANopen functionality is expanded, the major revision has to be incremented. The minor revision
number identifies different versions with the same CANopen behavior.
Index, sub-index Meaning
1018h 0
Number of entries
1018h 1
Vendor ID
1018h 2
Product code
1018h 3
Revision number (major revision number and minor revision number)
1018h 4
Serial number