MENU > Settings > Alarm
Alarm time-out (A333.2 / A333.3)
16617
Circuit
Setting range
Factory setting
1
0 . . . 250 s
15 s
If an alarm condition from either 'Alarm high' or 'Alarm low' is present for
a longer time than the set Alarm time-out (in seconds), the alarm function
is activated.
See also: "Alarm high" (ID no. 16614) and "Alarm low" (ID no. 16615).
0 - 250:
Set the time-out time.
X
= Time
Y
= Level
# 1 # = Actual level
# 2 # = Alarm high
# 3 # = Alarm low
# 4 # = Alarm time-out
ID no. overview for S7, S8, S9 and S10 alarm:
Alarm high
Alarm low
Alarm time-out
S7
14614
14615
14617
S8
13614
13615
13617
S9
12614
12615
12617
S10
11614
11615
11617
MENU > Settings > Alarm
Alarm high
1x614
Circuit
Setting range
Factory setting
1
0.0 . . . 25.0 bar
25.0 bar
Alarm is activated when the pressure (in bar) gets higher than the set value.
0.0 - 25.0:
Set the high alarm level
MENU > Settings > Alarm
Alarm low
1x615
Circuit
Setting range
Factory setting
1
0.0 . . . 25.0 bar
25.0 bar
Alarm is activated when the pressure (in bar) gets lower than the set value.
0.0 - 25.0:
Set the low alarm level.
VI.GU.T2.02
© Danfoss | 2017.09 | 127
Operating Guide ECL Comfort 310, application A333