MENU > Settings > Control parameters, refill pump(s)
Pressure des. (A333.2 / A333.3)
11321
Circuit
Setting range
Factory setting
1
0.2 . . . 25.0 bar
3.0 bar
Setting of desired pressure at S10 in order to speed control the refill pump(s)
P3 / P4.
0.2 - 25.0:
Set the desired pressure at S10 (in bar)
X
= Time
Y
= Pressure
# 1 # = Pressure desired
# 2 # = Actual pressure
# 3 # = Pressure difference
# 4 # = Neutral zone, Nz
# 5 # = Refill water pump
# 6 # = Speed control signal (0 - 10 V)
The parameter "Pressure des." is also used in application A333.1 for
setting desired pressure for ON / OFF control of refill pump(s) P3 / P4.
MENU > Settings > Control parameters, refill pump(s)
Xp (proportional band)
1x184
See Appendix “Parameter ID overview”
Set the proportional band. A higher value will result in a stable but
slow control of the flow temperature.