2.5.3 Electrical connections, 230 V a.c., power supply, pumps, dampers, motorized control valves etc.
Connections for A333.3, in general:
See also the Mounting Guide (delivered with the application key) for application specific connections.
Application A333.3
Terminal
Description
Max. load
19
Phase for ON / OFF valve / Alarm
18
A1
Alarm
4 (2) A / 230 V a.c.*
17
V2
ON / OFF valve for pressure release
4 (2) A / 230 V a.c.*
16
Phase for refill water pump
15
P4
Refill water pump
4 (2) A / 230 V a.c.*
14
Phase for circulation pumps / refill water pump
13
P3
Refill water pump
4 (2) A / 230 V a.c.*
12
P2
Circulation pump
4 (2) A / 230 V a.c.*
11
P1
Circulation pump
4 (2) A / 230 V a.c.*
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
8
Not to be used
7
Not to be used
6
Not to be used
5
Phase for ON / OFF valve V1
4
V1
ON / OFF valve for refill water
0.2 A / 230 V a.c.
3
Not to be used
0.2 A / 230 V a.c.
2
Not to be used
0.2 A / 230 V a.c.
1
Not to be used
0.2 A / 230 V a.c.
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
VI.GU.T2.02
© Danfoss | 2017.09 | 23
Operating Guide ECL Comfort 310, application A333