MENU > Settings > S7, S8, S9, S10 pressure
Low X (S7, S8, S9, S10)
1x607
Circuit
Setting range
Factory setting
1
0.0 . . . 10.0 V
2.0 V
Definition of which voltage value corresponds to which pressure value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and
is applied to input S7 (S8, S9, S10).
This input voltage is converted to display a pressure value (in bar).
See also "Pressure" and "High X".
X
= Volt
Y
= Pressure (bar)
# 1 # = Low X
MENU > Settings > S7, S8, S9, S10 pressure
High X (S7, S8, S9, S10)
1x608
Circuit
Setting range
Factory setting
1
0.0 . . . 10.0 V
10.0 V
Definition of which voltage value corresponds to which pressure value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and
is applied to input S7 (S8, S9, S10).
This input voltage is converted to display a pressure value (in bar).
See also "Pressure" and "Low X".
X
= Volt
Y
= Pressure (bar)
# 1 # = High X
VI.GU.T2.02
© Danfoss | 2017.09 | 123
Operating Guide ECL Comfort 310, application A333