MENU > Settings > Pump control
Retry time
11310
Circuit
Setting range
Factory setting
1
OFF / 1... 99 m
OFF
If an alarm has been generated for the pump or alarms have been generated
for both pumps, this setting will determine the time between the time of the
alarm and the retry time for repeated pump start.
OFF:
No retry time required after an alarm. The pump or
pumps in question will not be restarted.
1 ... 99:
After an alarm, the pump or pumps will be restarted
after the set time.
MENU > Settings > Pump control
Stab. time (stabilization time)
11313
Circuit
Setting range
Factory setting
1
1... 99 s
50 sec
Setting of max. time to elapse between pump start command and feedback
from differential pressure switch.
If the differential pressure switch does not give feedback within the set time,
the alarm will be activated and the other pump will get a start command.
If the chosen stabilization time (‘Stab. time’) is too short, the active
pump will stop immediately after the stabilization time has elapsed.
MENU > Settings > Pump control
Change, duration
11311
Circuit
Setting range
Factory setting
1
1 . . . 10 days
7 days
The number of days between shift of circulation pumps. The shift takes place
at the time set in 'Change time'.
X
= Time
# 1 # = Change duration
VI.GU.T2.02
© Danfoss | 2017.09 | 101
Operating Guide ECL Comfort 310, application A333