MENU > Settings > Refill tank
Filter constant
16113
Circuit
Setting range
Factory setting
1
1 - 250
4
The filter constant dampens the water level signal from the pressure
transmitter in order to make a stable read-out and related functions.
1:
Minor dampening (low filter constant)
250:
Major dampening (high filter constant)
MENU > Settings > Refill tank
Low X (A333.2 / A333.3)
16607
Circuit
Setting range
Factory setting
1
0.0 . . . 10.0 V
2.0 V
Definition of which voltage value corresponds to which water level value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and is
applied to input S12 (ECA 32).
This input voltage is converted to display a water level value (in meter).
See also "Level" and "High X".
X
= Volt
Y
= Level
# 1 # = Low X
MENU > Settings > Refill tank
High X (A333.2 / A333.3)
16608
Circuit
Setting range
Factory setting
1
0.0 . . . 10.0 V
10.0 V
Definition of which voltage value corresponds to which water level value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and is
applied to input S12 (ECA 32).
This input voltage is converted to display a water level value (in meter).
See also "Level" and "Low X".
X
= Volt
Y
= Level
# 1 # = High X
VI.GU.T2.02
© Danfoss | 2017.09 | 111
Operating Guide ECL Comfort 310, application A333