MENU > Settings > Flow / power limit
High T out X1 (flow / power limitation, high limit, X-axis)
1x119
Set the outdoor temperature value for the low flow / power limitation.
See Appendix “Parameter ID overview”
The corresponding Y coordinate is set in 'Low limit Y1'.
MENU > Settings > Flow / power limit
Low limit Y1 (flow / power limitation, low limit, Y-axis)
1x117
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1'.
See Appendix “Parameter ID overview”
The corresponding X coordinate is set in 'High T out X1'.
The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.
MENU > Settings > Flow / power limit
Low T out X2 (flow / power limitation, low limit, X-axis)
1x118
Set the outdoor temperature value for the high flow / power limitation.
See Appendix “Parameter ID overview”
The corresponding Y coordinate is set in 'High limit Y2'.
MENU > Settings > Flow / power limit
High limit Y2 (flow / power limitation, high limit, Y-axis)
1x116
Set the flow / power limitation referring to the outdoor temperature set
in 'Low T out X2'.
See Appendix “Parameter ID overview”
The corresponding X coordinate is set in 'Low T out X2'.
MENU > Settings > Flow / power limit
Adapt. time (adaptation time)
1x112
Controls how fast the flow / power limitation adapts to the desired
limitation.
See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor
value:
The desired temperature is adapted quickly.
Major
value:
The desired temperature is adapted slowly.
If the ‘Adapt. time’ is too low, there is a risk of unstable control.