MENU > Settings > Refill tank
Level, desired (A333.2 / A333.3)
16602
Circuit
Setting range
Factory setting
1
0.2 . . . 25.0 m
3.0 m
Setting of desired water level (measured by S12) in the refill water storage
tank.
See also "Stop difference" and "Start difference".
X
= Time
Y
= Level
# 1 # = Level, desired
# 2 # = Actual level
# 3 # = Stop difference
# 4 # = Start difference
MENU > Settings > Refill tank
Stop difference (A333.2 / A333.3)
16194
Circuit
Setting range
Factory setting
1
0.1 . . . 5.0 m
0.5 m
Setting the difference above the desired water level that will stop the filling of
the refill water storage tank (the valve V3 closes).
See also "Level, desired" and "Start difference".
MENU > Settings > Refill tank
Start difference (A333.2 / A333.3)
16195
Circuit
Setting range
Factory setting
1
-5.0 . . . -0.1 m
–0.5 m
Setting the difference below the desired water level that will start the filling of
the refill water storage tank (the valve V3 opens).
See also "Level, desired" and "Stop difference".
112 | © Danfoss | 2017.09
VI.GU.T2.02
Operating Guide ECL Comfort 310, application A333