Choosing a heat curve slope
The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.
MENU > Settings > Flow temperature
Temp. min.
1x177
See Appendix “Parameter ID overview”
Set the min. flow temperature for the system. The desired flow
temperature will not be lower than this setting. Adjust the factory
setting, if required.
‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
‘Temp. min.’ can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
MENU > Settings > Flow temperature
Temp. max.
1x178
See Appendix “Parameter ID overview”
Set the max. flow temperature for the system. The desired
temperature will not be higher than this setting. Adjust the factory
setting, if required.
The setting of ‘heat curve’ is possible for heating circuits only.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
VI.GU.T2.02
© Danfoss | 2017.09 | 75
Operating Guide ECL Comfort 310, application A333