MENU > Settings > Refill water
Pressure diff.
13322
Circuit
Setting range
Factory setting
1
0.1 . . . 5.0 bar
1.5 bar
Setting of the switching difference for the measured pressure at S10.
The difference is symmetrical around the 'Pressure des.'
See also 'Pressure des.'
0.1 - 5.0:
Set the desired switching difference related to the
pressure at S10.
X
= Time
Y
= Pressure
# 1 # = Pressure desired
# 2 # = Actual pressure
# 3 # = Pressure difference
MENU > Settings > Refill water
Max. pressure
11318
Circuit
Setting range
Factory setting
1
0.0 . . . 40.0 bar
40.0 bar
Setting of the max. acceptable pressure at S10.
When the pressure at S10 gets higher than set value, the release valve V2 is
opened in order to reduce the pressure.
See also "Max. press. diff."
0.0 - 40.0:
Set the max. acceptable pressure at S10.
X
= Time
Y
= Pressure
# 1 # = Max. pressure
# 2 # = Actual pressure
# 3 # = Max. pressure difference
VI.GU.T2.02
© Danfoss | 2017.09 | 105
Operating Guide ECL Comfort 310, application A333